1) Swing-type check valves are generally installed on horizontal pipelines: for check valves of DN~80mm, they can also be installed on vertical or upward-sloping pipelines.
2) Straight-through lift check valves should be installed on horizontal pipelines; vertical lift check valves must be installed on vertical pipelines, with the medium flowing from bottom to top.
3) Because check valves are easily damaged, the check valve should be installed close to the pump outlet, with a shut-off valve (generally a ball valve or gate valve) above the check valve for easy maintenance.
4) To make pressure release easy before dismantling the check valve, for check valves that do not have a drain valve of their own, a drain valve for pressure release should be installed between the check valve and the shut-off valve.