SIZING

    Flow Velocities of Common Media







    Flow Coefficient

    Concept and calculation of the flow coefficient


    The control valve, like an orifice plate, is a local resistance element. In the former, because the throttling area can be changed by the movement of the valve plug, it is a variable throttling element; in the latter, it is only that the bore diameter cannot be changed.

    However, we model the control valve as an orifice throttling form, see figure 2-1. For an incompressible fluid, substituting into the Bernoulli equation gives:

      Solving for  Let  Then, from the continuity equation Q =  AV, solving together with the above formula gives:

        V1 ,V2 —— velocities before and after throttling;
        V —— average flow velocity;
        P1 ,P2 —— pressures before and after throttling, 100KPa;
        A —— throttling area, cm;
        Q —— flow rate, cm/S;
       ξ—— resistance coefficient;
        r —— specific weight, Kgf/cm;
        g —— acceleration, g = 981cm/s ;
        If the above Q, P1, P2 and r are taken in engineering units, that is: Q ——m/ h; P1,P2 —— 100KPa;  r——gf/cm. Then formula (2) becomes:

       

    Further, let the coefficient of the flow Q,  , be Kv, that is: Kv = 
         
    This is the origin of the flow coefficient Kv. It can be seen that the greater the resistance of the valve, the smaller the Kv value; the larger the bore, the larger the Kv.   Flow coefficient formula for compressible fluids
        Because compressible fluids are considered from different angles, there are different calculation formulas; the two mainly used are the compressibility factor method and the average specific weight method.
        The compressibility factor method is obtained by multiplying the flow coefficient formula (4) for incompressible fluids by a compressibility factor ε, that is    

      where, ε——compressibility factor, determined by test as ε =  1-0.46△P/P1, in the
           saturated state,  △P/P1 = 0.5; at this time the flow no longer increases with the
           increase of △P, that is, choked flow occurs (choked flow is defined as:
           the maximum limit flow state reached when the fluid passes through the control valve),

      Pressure recovery factor FL
        In the derivation of the original formula from P1, it is considered that at the throttling point of the control valve the pressure drops directly from P1 to P2, as shown by the dashed line in figure 2-3. But in reality the pressure variation curve is as shown by the solid line in figure 2-3, and there is a difference in pressure recovery. Valves of different structures have different pressure recovery. The smaller the resistance of the valve, the stronger the recovery, the more it deviates from the pressure curve of the original derivation formula, and the greater the error between the result calculated by the original formula and the actual value. Therefore a coefficient FL representing the degree of pressure recovery of the valve is introduced to correct the original formula. FL is called the pressure recovery factor (Pressure reecvery factor), and its expression is:       (9)
    where , denote the pressure difference at the vena contracta when flashing occurs and the pressure difference across the valve.  
    Figure 2-3 Pressure recovery in the valve The key is the test problem of FL. Testing with a transparent valve body will reveal that when flashing occurs at the throttling point, that is, when a mass of bubbles is produced at the throttling point, Q basically no longer increases with the increase of △P. This test shows that:
    the critical pressure difference at which flashing occurs is the critical pressure difference at which choked flow occurs, so FL is also called the critical flow factor (Critical flow factor); therefore FL can both express the pressure recovery caused by different valve structures,
    to correct the flow coefficient calculation error caused by different valve structures, and be used to distinguish normal flow from choked flow, that is, the pressure difference △Pc in the defining formula (9) of FL is the critical pressure difference at which the tested valve produces choked flow.
    Thus, when △P<△Pc the flow is normal, and when △P≥△Pc the flow is choked.  

    Type of control valve

    Flow direction

    FL value


    Single-
    seat
    control
    valve

    Plunger-type plug

    Flow-to-open

    0.90

    Flow-to-close

    0.80

    “V”-port plug

    Any flow direction

    0.90

    Cage-type plug

    Flow-to-open

    0.90

    Flow-to-close

    0.80

    Double-seat
    control valve

    Plunger-type plug

    Any flow direction

    0.85

    “V”-port plug

    Any flow direction

    0.90

    Angle control valve

    Plunger-type plug

    Flow-to-open

    0.80

    Flow-to-close

    0.90

    Cage-type plug

    Flow-to-open

    0.85

    Flow-to-close

    0.80

    Venturi type

    Flow-to-close

    0.50

    Ball valve

    “O” type

    Any flow direction

    0.55

    “V” type

    Any flow direction

    0.57

    Butterfly valve

    60° full open

    Any flow direction

    0.68

    90° full open

    Any flow direction

    0.55

    Eccentric rotary valve

     

    Flow-to-open

    0.85

       