    Control Valve Performance Testing

      The performance indicators of a pneumatic control valve are: basic error, return difference, dead band, start and end point deviation, rated travel deviation, leakage, tightness, pressure strength, appearance, rated flow coefficient, inherent flow characteristic, vibration resistance and operating life, 13 items in total, of which the first 9 are factory inspection items. Because of factors such as transportation of the control valve and adjustment of the working spring range, the following performance items often need to be adjusted and checked before installation:
      1) Basic error
      Apply the specified input signal smoothly in the increasing and decreasing directions to the actuator chamber (or positioner), measure the travel value corresponding to each point, and calculate the error at each point between the actual “signal-travel” relationship and the theoretical relationship. Its maximum value is the basic error. The test points should at least include the 5 points of 0, 25%, 50%, 75% and 100% of the signal range. The basic error limit of the measuring instrument should be less than 1/4 of the basic error limit of the valve under test.
       2) Return difference
       The test procedure is the same as described in point 1) above. The maximum difference measured at the same input signal for the upscale and downscale travel is the return difference.
       3) Start and end point deviation
       The method is the same as point 1). The basic error at the upper limit (start point) of the signal is the start point deviation; the basic error at the lower limit (end point) of the signal is the end point deviation.
      4) Rated travel deviation
       Apply the rated input signal to the pneumatic actuator chamber (or positioner) so that the valve stem travels the full stroke; the ratio of the difference between the actual travel and the rated travel to the rated travel is the rated travel deviation. The actual travel must be greater than the rated travel.
      5) Leakage
       The test medium is a clean gas (air and nitrogen) or liquid (water or kerosene) at 10~50℃; test procedure A is: when the allowable differential pressure of the valve is greater than 350KPa, the test pressure is 350KPa; when it is less than 350KPa, the allowable differential pressure is used; test procedure B uses the maximum working differential pressure of the valve. The test signal pressure should ensure that the valve is in the closed state. In test procedure A, the signal pressure of the actuator of an air-to-open valve is zero; the signal pressure of the actuator of an air-to-close valve is the upper limit value of the input signal plus 20KPa; the signal pressure of the actuator of a two-position valve should be the value specified in the design. In test procedure B, the signal pressure of the actuator should be the value specified in the design. The test medium should be admitted into the valve in the specified flow direction; the valve outlet may be directly connected to the atmosphere or connected to a measuring device with low pressure loss whose outlet is open to the atmosphere; leakage may be measured only after it is confirmed that the valve and the downstream connecting pipes are completely filled with the medium.

    Main performance and testing of electric control valves

    The main performance indicators of an electric control valve are: basic error, return difference, dead band, rated travel deviation, leakage, tightness, pressure strength, appearance, rated flow coefficient, inherent flow characteristic, vibration resistance, temperature, long-term working reliability, explosion protection, damping characteristic, influence of supply voltage variation, influence of ambient temperature variation, insulation resistance, insulation strength, etc. The requirements and test methods for the first 10 indicators are the same as or similar to those for pneumatic valves, among which basic error, return difference, dead band, leakage, tightness, appearance, damping characteristic, influence of supply voltage variation and insulation resistance are factory test items; the requirements and test methods for the last 3 performance indicators are:

     1) Damping characteristic
    The damping characteristic of an electric control valve is specified as the valve stem oscillating no more than 3 “half cycles” in both the upscale and downscale directions. The test method is to apply signals of 20%, 50% and 80% of the input signal range at the input end respectively and observe the number of “half cycle” oscillations of the valve stem at the corresponding positions of the upscale and downscale travel.
     2) Influence of supply voltage variation
     When the supply voltage of the electric control valve varies within the range of 220+20 -30V, the change in valve stem displacement should not exceed 1.5% of the full stroke. The test method is: at a supply voltage of 220V, apply a signal of 20% of the signal range at the input end and measure the corresponding valve stem travel value, then adjust the supply voltage to 190V and 240V and measure the corresponding change in valve stem travel; then apply signals of 50% and 80% of the signal range in turn and measure the change in valve stem travel.
     3) Insulation resistance
     When the ambient temperature is 10~35℃ and the relative humidity does not exceed 85%, the insulation resistance of the electric control valve shall meet the following requirements: not less than 20MΩ from each input terminal to the casing; not less than 50MΩ from each input terminal to the power terminals; not less than 50MΩ from the power terminals to the casing. The test method is to use a type 500 megohmmeter.
    Inspection of Control Valves

    The control valve is in direct contact with the process medium, and its performance directly affects the system quality and environmental pollution. Therefore, the pneumatic control valve must be maintained frequently and inspected periodically, and in severe service conditions and important applications, maintenance work should be given even more attention.
    Key inspection points
    1) Inner wall of the valve body
    For control valves used in high differential pressure and corrosive media service, the inner wall of the valve body and the diaphragm of diaphragm valves are constantly subjected to the impact and corrosion of the medium, so the pressure resistance and corrosion resistance must be inspected as key points.
    2) Valve seat
    When the control valve is working, because the medium penetrates in, the internal thread surface used to fix the valve seat is prone to corrosion, which may loosen the valve seat; attention should be paid to this during inspection. For valves working under high differential pressure, the seat sealing face should also be checked for erosion damage.
    3) Valve plug
    The valve plug is the moving part of the control valve when it is working and suffers the most serious erosion and corrosion by the medium; during maintenance, carefully check whether each part of the valve plug is corroded or worn, especially under high differential pressure where the wear of the valve plug is more serious (due to cavitation); attention should be paid to this. If the valve plug is seriously damaged it should be replaced; in addition, attention should also be paid to whether the valve stem shows a similar phenomenon, or whether its connection to the valve plug is loose.
    4) Diaphragm, “O” rings and other gaskets.
    The diaphragm, “O” sealing rings and other gaskets in the control valve should be checked for aging and cracking damage.
    5) Sealing packing
    Attention should be paid to whether the PTFE packing and the sealing grease are aged and whether the mating surfaces are damaged; they should be replaced when necessary.