Gas Transmission and Distribution Process
The task of a vaporization station is to receive LNG, vaporize it, and supply it to users or use it for seasonal peak shaving. A vaporization station may be located inside a storage and distribution station, in which case it is called a vaporization room.
A CNG filling station mainly receives gas from the trunk pipeline; after filtration, pressure regulation and metering, the gas enters the compressor for pressurization and, after drying, is sent to storage cylinders. When vehicles need to be refueled, the cylinder bank and the dispenser are controlled by a sequential program controller to refuel the vehicle. A CNG filling station may also be located inside a storage and distribution station.
After long-distance transmission, the gas is dedusted, pressure-regulated, metered and odorized in the distribution station, and then, through distribution networks at various levels and gas pressure regulating devices, is supplied to users safely, with guaranteed quality and quantity, as required by the users.
Gas pipelines can be divided by purpose into four types: gas transmission mains, transmission and distribution mains, distribution branches and gas-consuming pipelines. (1) Gas transmission main: refers to the pipeline that sends gas from the city gate station (or gas source plant) to the various high- and medium-pressure regulating stations in the city. They are generally high-pressure and sub-high-pressure pipelines.
(2) Transmission and distribution main: the collective term for transmission pipes and distribution pipes. Because in urban medium-pressure gas pipeline systems very few pipes serve purely as transmission pipes, and in most cases the transmission pipe also serves as a distribution pipe, they are collectively called transmission and distribution mains.
① Medium-pressure transmission and distribution main: refers to the pipeline that sends gas from the gas source plant or storage and distribution station to the various gas-consuming areas of the city, including the plant outlet pipe, the station outlet pipe and main urban road pipes;
② Low-pressure transmission and distribution main: refers to the pipeline that sends gas from the regulating station to the gas supply area and distributes it to various users along the way.
Low-pressure gas transmission mains generally have no valves. When maintenance or fault handling is carried out on low-pressure pipelines, rubber balls can be used to plug the pipeline, or a water seal can be used instead of a valve to perform the shut-off function. On high-pressure and medium-pressure gas mains, sectional valves shall be provided, and valves shall also be provided at the starting points of their branch pipes. Valves shall be provided on the inlet and outlet pipes of the regulating room, at both ends of river-crossing gas pipelines and on both sides where they intersect railway or highway trunk lines. Valves should be installed only where absolutely necessary, so that when maintenance, fault handling or reconstruction is carried out, individual pipeline sections can be shut off and interruption of gas supply to a large area of users can be avoided. Of course, each additional valve increases both the investment and the possibility of gas leakage. However, providing valves means that in the event of a fault only a small number of users, rather than a large number, will have their gas supply interrupted, which in turn improves the reliability of gas supply through the network.
City gate stations and storage and distribution stations shall have the main functions of filtration, pressure regulation, metering, gas quality testing, safety relief, safety shut-off, and automatic switching between the duty line and the standby line, and are required, on the premise of ensuring accurate pressure regulation and flow metering, to be designed with multiple safety measures so as to ensure the long-term, safe and stable use of gas.
I. Classification of regulating stations
(1) By regulation level 1. High- and medium-pressure regulating station 2. High- and low-pressure regulating station 3. Medium- and low-pressure regulating station
(2) By purpose 1. District regulating station 2. Dedicated regulating station 3. Box-type regulating device
(3) By installation arrangement
1. Above-ground regulating station
2. Underground regulating station
II. The installation of pressure regulating devices shall meet the following requirements:
(1) When natural conditions and the surrounding environment permit, it should preferably be installed in the open air, but a fence, guardrail or vehicle barrier shall be provided; (2) When installed in a separate above-ground regulating box (wall-mounted), the gas inlet pressure for residential and commercial users shall not be greater than 0.4 MPa; for industrial users (including boilers) the gas inlet pressure shall not be greater than 0.8 MPa
(3) When installed in a separate above-ground regulating cabinet (floor-standing), the gas inlet pressure for residential, commercial and industrial users (including boilers) should preferably not be greater than 1.6 MPa;
(4) When the requirements are met, it may be installed in a separate above-ground building;
(5) When restricted by above-ground conditions and the inlet pressure of the regulating device is not greater than 0.4 MPa, it may be installed in a separate underground building or a separate underground box, and shall meet certain requirements;
(6) Regulating devices for liquefied petroleum gas and for gas with a relative density greater than 0.75 shall not be installed in basements, semi-basements or separate underground boxes.
Industrial enterprises and public utility users usually have a large gas consumption and can use gas at higher pressure; therefore, it is more reasonable for these users to be connected to medium-pressure or high-pressure gas pipelines. This not only reduces the load on the low-pressure gas network but also makes full use of the gas pressure itself to induce air. Therefore, both the inlet and the outlet of a dedicated regulating station can use a relatively high pressure.
Usually a separate room adjacent to the combustion equipment is used as the dedicated regulating station, as shown in Figure 3-8.
When the inlet pressure is medium or low pressure and only one regulator with a connection diameter of less than 50 mm is installed, the regulator may also be located in a corner of the workshop where the gas is used. If it is installed inside the workshop, it should be isolated with a fence. The regulating equipment and safety equipment must be checked frequently for normal operation. The gas tightness of the piping must also be checked frequently.
A flow meter shall be installed in a dedicated regulating station. A single-seat regulator that closes tightly should be selected, and a safety shut-off valve should be selected as the safety device. The gas passage must be shut off not only when the pressure is too high but also when the pressure is too low. This is because too low a pressure may cause the burner flame to go out, filling the combustion chamber with gas and forming an explosive gas mixture, which may cause an accident when the flame approaches or when ignition is attempted again.
The load of a regulating station is the gas supply capacity that the station can handle. The load of a regulating station is considered as follows:
1. When there is only one regulator in the regulating station, it should bear the entire gas supply, and the flow rate of the regulator must meet the following requirements:
(1) The rated flow of the regulator shall be determined as 1.x times the maximum hourly transmission volume of the pipeline network served by the regulator;
(2) The regulator flow rate shall meet the requirements of the maximum and minimum inlet gas pressures;
(3) The pressure difference across the regulator shall be determined as the difference between the lowest design pressure of the gas pipeline upstream of the regulator and the upper limit of the design pressure of the gas pipeline downstream of the regulator.
Process requirements for regulating stations (or regulating boxes, regulating cabinets):
(1) District regulating stations in areas where the low-pressure network is not looped, and user regulating devices for continuous production, should preferably be provided with standby regulators; in other cases a standby regulator may be omitted. A bypass pipe shall be provided between the gas inlet and outlet pipes of the regulator; a user regulating box (wall-mounted) may omit the bypass pipe;
(2) Valves must be provided on the outdoor inlet and outlet pipes of high-pressure and sub-high-pressure gas regulating stations;
(3) A filter shall be installed at the regulator inlet;
(4) At the regulator inlet (or outlet), an overpressure protection device shall be provided, and it should preferably be of the manual-reset type; (5) Indicating pressure gauges shall be provided upstream and downstream of the regulator and the filter;
(6) A recording pressure instrument shall be provided downstream of the regulator; the mouth of the relief pipe shall be at least 1.0 m above the eaves of the regulating station. 17. The arrangement of the regulators in the regulating station shall meet the following requirements:
The horizontal installation height of the regulator shall facilitate maintenance and repair; when two or more regulators are arranged in parallel, the clear distance between the outer edges of adjacent regulators should preferably be greater than 1 m; the clear distance between the regulator and the wall surface and the width of the main indoor passage shall both be greater than 0.8 m; when the gas pipelines inside and outside the regulating station are connected by insulating joints, the regulator and its auxiliary equipment must be grounded, and the grounding resistance shall be less than 100 ohms.
When the city uses a low-pressure gas source and the scale of gas supply is not particularly large, the gas supply system usually adopts low-pressure gas storage, and correspondingly a low-pressure storage and distribution station needs to be built. The function of a low-pressure storage and distribution station is to store the surplus gas during the off-peak period and, during the peak period, to draw the gas from the low-pressure storage tanks and pressurize it into the medium-pressure network by means of the compressors of the storage and distribution station, so as to ensure normal gas supply.
When gas is supplied directly to domestic users from a medium-pressure network (or a low-pressure network at higher pressure), the gas pressure should be reduced directly to the rated pressure of normal operation of the gas appliances by a user regulator. In this case the user regulator is often mounted in a metal box and hung on the wall, as shown in Figure 3-9. When the box-type regulating device is installed in dense building groups, the safety relief valve may be omitted and only the safety shut-off valve used.
Valves for Gas Service
There are many types of valves; those commonly used on natural gas pipelines include gate valves, globe valves, ball valves and butterfly valves.
1. Filter
When its inlet pressure is greater than 0.2 MPa, the allowable pressure loss (upper limit) of the filter is 10 kPa:
When the inlet pressure of the regulating station is 0.2 MPa or less, the allowable pressure loss (upper limit) of the filter is 5 kPa. If the allowable pressure loss is exceeded, the filter should be inspected and cleaned or its filter element replaced.
2. Safety relief valve
The relief pressure of the regulating station should be slightly higher than the shut-off pressure; generally the relief pressure is taken as about 1.3 times the rated outlet pressure.
3. Safety shut-off valve
The working pressure of the safety shut-off valve should be slightly higher than the safety relief pressure. Depending on the circumstances, it may be taken as 1.1~1.2 times the relief pressure.
For example, for a regulating station with an outlet pressure P2n = 1500 Pa, the working pressure of the safety relief valve may be taken as Pf = 2000 Pa, while the working pressure of the safety shut-off valve may be taken as Pshut = 2300 Pa.
Process Parameters of Regulating Stations
The purpose of providing a regulating station is to establish a pressure-stable pipeline network system downstream of it, meeting the needs of users for safe gas supply and gas usage; at the same time, the regulating station itself must be able to operate safely and reliably. For this reason, both the construction and the operation of the regulating station must meet the requirements of normal operating condition indices. Here the several indices of inlet pressure and outlet pressure are mainly introduced.
Maximum inlet pressure P1max
Refers to the highest inlet pressure value allowed for the regulating station within the specified pressure range.
The maximum inlet pressure P1max shall be indicated on the nameplate of the regulator product. Users should select a regulator suitable for their own pipeline network pressure system according to the product nameplate and the operating instructions.
Minimum inlet pressure P1min
Refers to the lowest inlet pressure value allowed within the specified pressure range. A regulating station can only meet the requirements of supplying a certain number of users; otherwise the outlet pressure of the regulating station cannot be kept within the qualified pressure range, which will affect safe and normal gas supply. If the station inlet pressure is lower than the minimum inlet pressure P1min, the gas supply capacity of the regulating station will be lower than the rated flow, resulting in too low an outlet pressure and a situation in which gas supply cannot be guaranteed.
Rated outlet pressure P2n.
When the outlet pressure of the regulating station is adjusted to a specified value within the specified pressure class range, this pressure value is the rated outlet pressure value of the regulating station. It may also be called the outlet pressure setpoint.
Regulation accuracy óP2
Refers to the ratio of the pressure difference by which the outlet pressure of the regulating station deviates from the rated outlet pressure P2n to the rated outlet pressure P2n.
The smaller the regulation accuracy, the more stable the operating condition of the regulating station; the larger it is, the more unstable the operating condition. According to the requirements of the code, the permitted regulation accuracy of a regulating station with a low-pressure outlet is ±15%; that of a regulating station with a medium-pressure class B outlet is ±10%; that of a regulating station with a high-pressure or medium-pressure class A outlet is ±5%. If the regulation accuracy exceeds the above percentages, the operating condition is unstable and the operating parameters of the regulating station are unqualified. For example, for a regulating station with a rated outlet pressure of 1.5 kPa, the permitted regulation accuracy of the regulating station is ±15%; therefore its maximum outlet pressure P2max
= 1500 Pa × 1.15 = 1725 Pa, and its minimum outlet pressure is P2min = 1500 Pa × 0.85 = 1275 Pa
Rated flow Qn
When the inlet pressure of the regulating station is the minimum allowed value P1min and the outlet pressure is the minimum value P2min allowed by the regulation accuracy δP2,
the gas flow of the regulating station is the rated flow Qn.
If the regulating station works normally and the inlet pressure is also normal, its flow will be greater than or equal to the rated flow. If the flow in the outlet network supplied by the regulating station does not exceed this rated flow, the station outlet pressure will meet the regulation accuracy requirement; conversely, if the consumption in the network connected to the outlet of the regulating station is greater than this rated flow, the outlet pressure P2 will drop and very likely fall below the minimum outlet pressure P2min, so that it cannot meet the regulation accuracy requirement.
When determining the gas supply scope and the number of households of a regulating station, this factor should be fully considered; overload operation will result in too low a gas supply pressure.
Shut-off pressure Pb
When the flow of the regulating station gradually decreases and its flow equals zero, the stable pressure value reached on the output side is the shut-off pressure.
Zero flow is an unfavorable operating condition for the regulator, and it often makes the outlet pressure of the regulating station exceed the maximum outlet pressure P2max allowed by the permitted regulation accuracy. For this reason, the code specifies the allowable shut-off pressure value for regulating stations.
The allowable shut-off pressure value of a regulating station with a low-pressure outlet is Pb = 1.25P2n; the allowable shut-off pressure value of a regulating station with a medium-pressure class B outlet is Pb = 1.20P2n; the allowable shut-off pressure of a regulating station with a medium-pressure class A or high-pressure outlet is Pb = 1.15P2n
The shut-off pressure is a very important technical index of a regulating station. If the outlet pressure cannot be shut off, the pipeline network is likely to be over-pressurized, causing accidents such as damage to gas meters, fire, explosion and poisoning. Therefore, it is very important to control the shut-off pressure below the allowable shut-off pressure value.
Maximum outlet pressure P2max
Refers to the highest outlet pressure value allowed within the specified regulation accuracy range.
Minimum outlet pressure P2min
Refers to the lowest outlet pressure value of the regulating station allowed within the specified regulation accuracy range.
The rated outlet pressure P2n is a standard for the outlet pressure P2 determined according to the needs of the pipeline network and the users.
P2max and P2min are both defined on the basis of P2n and are the allowable pressure fluctuation ranges of the outlet pressure P2n; otherwise the regulation condition is unqualified and cannot meet the actual needs of the pipeline network and the users. Moreover, gas combustion will be unsafe and unstable and will fail to meet the combustion hygiene standards.