    LNG Production Process

    Liquefaction temperatures of common hydrocarbon gases
    methane -163 °C  natural gas -161.2 °C  ethylene -104 °C   ethane -83.3 °C  acetylene -84 °C  propylene -47.7 °C  propane -45 °C

    Process flow: LNG is delivered by cryogenic road tanker to the LNG satellite station; the horizontal dedicated unloading booster installed at the unloading bay pressurizes the road tanker tank, and the pressure difference is used to send the LNG to the cryogenic LNG storage tank of the satellite station. Under working conditions, the tank booster pressurizes the LNG in the tank to 0.6 MPa. The pressurized cryogenic LNG enters the ambient-air vaporizer, where it exchanges heat with the air and is converted into gaseous natural gas with a raised temperature; the outlet temperature is 10℃ lower than the ambient temperature and the pressure is 0.45-0.60 MPa. When the temperature of the natural gas at the outlet of the ambient-air vaporizer does not reach 5℃ or above, it is heated by a water-bath heater, and finally, after pressure regulation (the outlet pressure of the regulator is 0.35 MPa), metering and odorization, it enters the city gas distribution network and is supplied to various users.


    LNG is the abbreviation of liquefied natural gas, whose main component is methane. The natural gas produced in the gas field is first purified and treated, and then liquefied under cryogenic temperature (-162℃) and pressure to form liquefied natural gas. LNG is colorless, odorless, non-toxic and non-corrosive; its volume is about 1/600 of the volume of the same amount of gaseous natural gas; its boiling point at atmospheric pressure is -161.5℃, its storage temperature at atmospheric pressure is -162.3℃, and its density is about 430 kg/m3.

    The design temperature of the storage tank reaches minus 196 (the boiling point of LNG at normal temperature is minus 162 degrees Celsius), while the temperature of the natural gas leaving the station is required to be no lower than 10 degrees Celsius below the ambient temperature.
    In the design of LNG vaporization stations, the design codes commonly adopted are: GB 50028-93 "Code for Design of City Gas Engineering" (2002 edition), GBJ 16-87 "Code for Fire Protection Design of Buildings" (2001 edition), GB 50183-2004 "Code for Fire Protection Design of Oil and Gas Engineering", and the American NFPA-59A "Standard for the Production, Storage, and Handling of Liquefied Natural Gas".
    During normal operation the working temperature of the LNG storage tank is -162.3℃; before it is first put into service, the tank must be pre-cooled with liquid nitrogen at -196℃
    BOG buffer tank  BOG heater: Boil Off Gas, i.e. boil-off gas
    Ambient-air vaporizer
    Water-bath natural gas heater: when the ambient temperature is low and the temperature of the gaseous natural gas at the outlet of the ambient-air vaporizer is below 5℃, a water-bath natural gas heater is connected in series after the ambient-air vaporizer to heat the vaporized natural gas
    Safety relief gas (EAG) heater: when LNG is vaporized into gaseous natural gas, its critical buoyancy temperature is -107℃. When the temperature of the gaseous natural gas is higher than -107℃, the gaseous natural gas is lighter than air and will rise from the leak and drift away. When the temperature of the gaseous natural gas is lower than -107℃, the gaseous natural gas is heavier than air, and the cryogenic gaseous natural gas will accumulate downward and form a flammable explosive mixture with air. In order to prevent the cryogenic gaseous natural gas released by the safety valve from accumulating downward and forming an explosive mixture, one ambient-air safety relief gas heater is provided; the relief gas is first heated by this heater so that its density becomes lower than that of air, and is then led to high-level relief. For LNG vaporization stations in the south that are not equipped with an EAG heating device, in order to prevent the cryogenic LNG gas-liquid mixture released after the safety valve opens from causing cold burns to operators, the relief pipe of each individual safety valve and the relief pipe of the storage tank should be connected to a centralized relief header for relief.

    Pressure regulating, metering and odorization devices: the scale of the LNG vaporization station determines the selection of the pressure regulating device. Usually 2 pressure-regulating trains are provided, and the regulator selected is a self-operated regulator with a pilot and overpressure shut-off. The odorant used is tetrahydrothiophene
    Valves in the process system shall meet the pressure and flow requirements for conveying LNG, and at the same time must have low-temperature performance down to -196℃. The commonly used LNG valves mainly include booster control valves, pressure-reducing control valves, emergency shut-off valves, cryogenic globe valves, safety valves, check valves, etc. The valve material is 0Cr18Ni9.

    Pipes with a medium temperature ≤ -20℃ use stainless steel seamless steel tubes for fluid service (GB/T 14976-2002), with material 0Cr18Ni9. All pipe fittings use seamless stamped fittings of material 0Cr18Ni9 (GB/T 12459-90). Flanges use male-female face long-neck butt-welding steel pipe flanges (HG 20592-97), with material 0Cr18Ni9. Flange gaskets use spiral-wound metal gaskets of material 0Cr18Ni9. Fasteners use dedicated stud bolts and nuts of material 0Cr18Ni9.
    For process piping with a medium temperature >-20℃, when the nominal diameter is ≤200 mm, seamless steel tubes for fluid service (GB/T8163-1999) of material No. 20 steel are used; when the nominal diameter is >200 mm, welded steel tubes (GB/T 3041-2001) of material Q235B are used. All pipe fittings use seamless stamped fittings of material No. 20 steel (GB/T 12459-90). Flanges use raised-face neck butt-welding steel pipe flanges (HG 20592-97) of material No. 20 steel. Flange gaskets use flexible graphite composite gaskets (HG 20629-97).
    LNG piping usually uses austenitic stainless steel tubes of material 0Cr18Ni9; although they have excellent low-temperature mechanical properties, the cold shrinkage rate is as high as 0.003
    During normal operation, the operating pressure of the LNG storage tank must be controlled within the allowable range. The normal working pressure range of LNG storage tanks in South China is 0.3-0.7 MPa. When the pressure in the tank is lower than the set value, the self-pressurization vaporizer and the self-pressurization valve can be used to pressurize the storage tank. The lower pressurization limit is determined by the opening pressure of the self-pressurization valve, and the upper pressurization limit is determined by the automatic closing pressure of the self-pressurization valve, which is usually about 15% higher than the set opening pressure of the self-pressurization valve. For example: when LNG is used as the main gas source of city gas, if the opening pressure of the self-pressurization valve is set at 0.6 MPa, the closing pressure of the self-pressurization valve is about 0.69 MPa, and the pressurization value of the storage tank is 0.09 MPa. The maximum working pressure of the storage tank is limited by the set pressure (upstream pressure) of the automatic pressure-reducing control valve installed on the cryogenic gas-phase pipeline of the tank. When the maximum working pressure of the tank reaches the set opening value of the pressure-reducing control valve, the pressure-reducing valve opens automatically to release the pressure, so as to protect the safety of the tank. To ensure that the pressurization valve and the pressure-reducing valve do not interfere with each other during operation, the closing pressure of the pressurization valve and the opening pressure of the pressure-reducing valve must not overlap, and a pressure difference of more than 0.05 MPa should be ensured. Considering the manufacturing accuracy of the two valves, the appropriate pressure difference should be determined during equipment commissioning.

    During storage, LNG will slowly evaporate due to the "ambient heat leakage" of the storage tank (daily static evaporation rate by volume ≤0.3%), causing the pressure in the tank to rise gradually and eventually endangering the safety of the tank. To ensure the safe operation of the tank, the design adopts three levels of safety protection measures — the tank pressure-reducing control valve, the pressure-alarm manual relief, and the safety valve opening — for overpressure protection of the tank.

    The protection sequence is: when the tank pressure rises to the set opening value of the pressure-reducing control valve, the pressure-reducing control valve opens automatically to release gaseous natural gas; when the pressure-reducing control valve fails and the pressure in the tank continues to rise and reaches the pressure alarm value, a pressure alarm is given and manual relief is used to reduce the pressure; when the pressure-reducing control valve fails and the manual relief has not been opened, the safety valve opens to release the pressure, ensuring the safe operation of the LNG storage tank. For an LNG storage tank with a maximum working pressure of 0.80 MPa, the design pressure is 0.84 MPa, the set opening pressure of the pressure-reducing control valve is 0.76 MPa, the tank alarm pressure is 0.78 MPa, the safety valve opening pressure is 0.80 MPa, and the safety valve discharge pressure is 0.88 MPa

    To prevent LNG from rolling over and causing accidents, stratification of the LNG in the tank must be prevented. The following measures are commonly adopted.

    ① Store LNG from different gas sources separately, to avoid LNG stratification caused by density differences.

    ② To prevent a density difference between the LNG injected into the tank at different times, the following filling methods are adopted:

    a. When the density of the LNG in the tanker is close to that of the LNG in the tank, fill through the lower liquid inlet of the tank; b. When light LNG in the tanker is filled into a tank containing heavy LNG, fill through the lower liquid inlet of the tank; c. When heavy LNG in the tanker is filled into a tank containing light LNG, fill through the upper liquid inlet of the tank. ③ The liquid inlet pipe in the tank uses mixing nozzles and perforated pipes, which can fully mix the newly filled LNG with the existing LNG, thereby avoiding stratification.

    ④ For LNG stored for a long period, periodic tank switching is adopted to prevent stratification caused by standing still.


    Operation monitoring and safety protection

    ① High and low liquid level emergency shut-off of the LNG storage tank. A pneumatic emergency shut-off valve is installed on both the liquid inlet pipe and the liquid outlet pipe of each LNG storage tank; in an emergency, the inlet and outlet liquid lines can be shut off at the unloading bay, the tank area and the control room. Pipeline safety valves are installed respectively on the inlet and outlet lines of the liquid inlet emergency shut-off valve and on the outlet line of the liquid outlet emergency shut-off valve, to release the pressure of the pipeline after the emergency shut-off valve is closed.

    ② Over-limit temperature alarm after the vaporizer, with interlock shutting off the vaporizer liquid inlet line. The focus is on detecting, alarming and interlocking the gas temperature at the vaporizer outlet. During normal operation, when the rated load is reached, the gas outlet temperature of the vaporizer is 10℃ lower than the ambient temperature. When the vaporizer is frosted excessively or malfunctions, the vaporizer is controlled by over-limit temperature detection and alarm and interlock shut-off of the vaporizer liquid inlet line.

    ③ Natural gas leakage concentration detectors are installed in the LNG process unit area. When the concentration exceeds the alarm limit value, audible and visual alarm signals are given, and the inlet and outlet electric valves can be closed quickly in the control room.

    ④ Select overpressure shut-off type regulators. When the regulator outlet pressure is over-pressurized, it switches over automatically. A safety relief valve is provided after the regulator for relief in case of overpressure.

    ⑤ Electric valves are provided on all natural gas outlet lines of the station, which can be shut off quickly in the control room.

    ⑥ The pressure after the outlet valve is higher than the set alarm pressure