Working principle of solenoid valves
    A solenoid valve consists of a solenoid coil and a magnetic core and is a valve body containing one or more ports. When the coil is energised or de-energised, the movement of the core makes the fluid pass through the valve body or be cut off, so as to change the direction of the fluid. The electromagnetic part consists of a fixed core, a movable core, a coil, etc.; the valve body part consists of a spool, a sleeve, a spring seat, etc. The coil is mounted directly on the valve body, and the valve body is enclosed in a sealed tube, forming a simple, compact assembly.

    By principle, solenoid valves fall into three main types: direct-acting, step direct-acting and pilot-operated. In terms of air or oil circuits, the solenoid valves commonly used in production are two-position three-port, two-position four-port, two-position five-port, etc. "Two positions" means the spool of the solenoid valve has two different working positions (open and closed), while "how many ports" refers to the number of ports on the valve body; for example, a two-position two-port solenoid valve has one inlet and one outlet (two ports, the most common type), a two-position three-port solenoid valve controls liquid with one inlet and two outlets (one normally open and one normally closed), a pneumatic directional solenoid valve has one inlet, one outlet and one exhaust, and a hydraulic one has one inlet, one outlet and one return.

    By structural principle, solenoid valves fall into three main types:

    1) Direct-acting solenoid valve:
    Principle: when energised, the coil produces an electromagnetic force that lifts the closing member off the seat and opens the valve; when de-energised, the electromagnetic force disappears and the spring presses the closing member onto the seat, closing the valve.
    Features: works normally under vacuum, negative pressure and zero pressure, but the bore generally does not exceed 25 mm.

    2) Step direct-acting solenoid valve:
      Principle: this combines the direct-acting and pilot-operated principles. When there is no pressure difference between inlet and outlet, on energisation the electromagnetic force lifts the small pilot valve and then the main valve closing member in turn, opening the valve. When the starting pressure difference exists between inlet and outlet, on energisation the electromagnetic force acts on the small pilot valve, the pressure in the lower chamber of the main valve rises and that in the upper chamber falls, so the pressure difference pushes the main valve open; on de-energisation the pilot valve uses spring force or medium pressure to push the closing member downwards and close the valve.
      Features: it also operates at zero pressure difference, under vacuum or at high pressure, but the power is higher and horizontal installation is required.

    3) Pilot-operated solenoid valve:
      Principle: on energisation the electromagnetic force opens the pilot port, the pressure in the upper chamber drops rapidly and a pressure difference is formed around the closing member that is low above and high below, so the fluid pressure pushes the closing member upwards and opens the valve; on de-energisation the spring force closes the pilot port, and through the bypass port the inlet pressure quickly forms a pressure difference around the closing member that is low below and high above, so the fluid pressure pushes the closing member downwards and closes the valve.
      Features: a higher upper limit of the fluid pressure range, and it can be installed in any position (custom versions required), but the fluid pressure difference condition must be met.


    Classification of solenoid valves by circuit

    Two-position three-port solenoid valve:
    In terms of the air circuit (or liquid circuit), a two-position three-port solenoid valve has one inlet port (connected to the air supply), one outlet port (supplying air to the target equipment) and one exhaust port (usually fitted with a silencer, which may be omitted if noise is not a concern). Electrically it is generally single-solenoid (single coil). Two-position three-port valves are divided into normally closed and normally open types: normally closed means the air circuit is cut off when the coil is not energised, and normally open means the air circuit is open when the coil is not energised. Operating principle of the normally closed two-position three-port solenoid valve: energise the coil and the air circuit opens; as soon as the coil is de-energised the air circuit closes - this is equivalent to "jogging". Operating principle of the normally open two-position three-port single-solenoid valve: energise the coil and the air circuit closes; as soon as the coil is de-energised the air circuit opens - this is also "jogging".

    Fig. 1 shows a simple sectional view of the structure and the working principle of a two-position three-port direct-acting solenoid valve (normally closed). When the coil is energised, the fixed core produces an electromagnetic force; the spool moves upwards under this force and the seal lifts, so ports 1 and 2 are connected and ports 2 and 3 disconnected, and the valve is in the air-intake state and can control the action of a cylinder. When de-energised, the spool returns to its original position under the spring force, i.e. ports 1 and 2 are disconnected and ports 2 and 3 connected, and the valve is in the exhaust state.



    Two-position five-port solenoid valve
    A two-position five-port solenoid valve has one inlet port (air supply), one forward-action outlet port and one reverse-action outlet port (supplying the forward and reverse acting air supplies to the target equipment), and one forward-action exhaust port and one reverse-action exhaust port (fitted with silencers). Two-position five-port valves are generally double-solenoid (two coils). Operating principle of the two-position five-port double-solenoid valve: energise the forward-action coil and the forward-action air circuit opens (air at the forward-action outlet); even after the forward-action coil is de-energised the forward-action air circuit remains open, and this is maintained until the reverse-action coil is energised. Energise the reverse-action coil and the reverse-action air circuit opens (air at the reverse-action outlet); even after the reverse-action coil is de-energised the reverse-action air circuit remains open, and this is maintained until the forward-action coil is energised. This is equivalent to "self-locking".
    Fig. 2 shows a simple sectional view of the structure and the working principle of a two-position five-port direct-acting solenoid valve (normally closed). In the initial state ports 1 and 2 admit air and ports 4 and 5 exhaust; when the coil is energised the fixed core produces an electromagnetic force that actuates the pilot valve, compressed air passes through the air circuit into the pilot piston and starts the piston, the sealing face in the middle of the piston opens the passage, ports 1 and 4 admit air and ports 2 and 3 exhaust; when de-energised the spool returns to its original position under the spring force.


    Other solenoid valves with several positions and ports
    Two-position two-port solenoid valve:
    When the left solenoid coil is energised, the core overcomes the right spring force and other related resistances and pushes the piston, so that the passage from P to A is connected. When the left coil is de-energised, the right spring overcomes the gas resistance and other related resistances and pushes the piston, so that the passage from P to A is cut off.
    Two-position four-port solenoid valve:
    When the left solenoid coil is energised, the core overcomes the right spring force and other related resistances and pushes the piston, the passage P to A is connected and O to B is connected, and the valve push rod moves to the right under the pressure difference. When the left coil is de-energised, the core overcomes the spring, air pressure and other related resistances and pushes the piston, the piston returns under the spring force, passages P to B and O to A are connected, and the valve push rod moves to the left under the pressure difference.

    Three-position three-port solenoid valve:
    When the left solenoid coil is energised, the core overcomes the right spring force and other related resistances and pushes the piston, passage A to P is connected and compressed air flows normally, while passage A to O is blocked. When the right solenoid coil is energised, the core overcomes the right spring force and other related resistances and pushes the piston, passage A to O is connected and passage A to P is blocked. When both coils are de-energised, the springs at both ends push the piston to the middle position, maintaining the reset state and blocking inlet A.

    Three-position four-port solenoid valve:
    When the left solenoid coil is energised, the core pushes the piston, passage A to P is connected and B to O is connected. When the right solenoid coil is energised, the core pushes the piston, passage B to P is connected and A to O is connected. When both coils are de-energised, the piston returns under the spring force and all passages are blocked.

    Three-position five-port solenoid valve:
    When the left coil is energised, passage P to B is connected, air enters the right side of the cylinder and the pressure rises, while A to R is connected and the left side exhausts so the pressure falls, and the cylinder piston moves to the left. When the right coil is energised, passage P to A is connected, air enters the left side of the cylinder and the pressure rises, while B to S is connected and the right side exhausts so the pressure falls, and the cylinder piston moves to the right. When both coils are de-energised, the piston returns under the spring force and all passages are blocked, and the cylinder piston stays in its current state.

Selection of solenoid valves
    Pneumatic circuit solenoid valves:
    Number of positions and ports / direct-acting or pilot-operated / body material in the air path / coil terminal box material / bore / air supply pressure / power consumption / voltage / electrical connection / explosion protection grade and ingress protection grade: the explosion protection grade concerns mainly flameproof? intrinsically safe? increased safety? or no explosion protection (merely water and dust tight) / mounting method: pipe-mounted (threaded)? or plate-mounted (NAMUR flange)?

    Process solenoid valves:
    Number of positions and ports / nominal bore / flanged or threaded connection / medium name and corrosivity / temperature and pressure rating / sealing class / explosion protection grade (e.g. ExidIIBT4) and ingress protection grade (e.g. IP65) / power requirement (e.g. below 30 W) / electrical connection (e.g. 1/2 NPT), manual reset device fitted or not?

    Points to note when selecting solenoid valves   
    1. Suitability: the fluid in the pipeline must match the medium rated for the selected solenoid valve model. The fluid temperature must be lower than the rated temperature of the selected solenoid valve. The permissible liquid viscosity for a solenoid valve is generally below 20 CST; above 20 CST this must be stated. Working pressure difference: when the maximum pressure difference in the pipeline is below 0.04 MPa, direct-acting and step direct-acting types such as the ZS, 2W, ZQDF and ZCM series should be used; when the minimum working pressure difference is above 0.04 MPa, a pilot-operated (pressure-difference) solenoid valve may be used; the maximum working pressure difference should be below the maximum rated pressure of the solenoid valve; solenoid valves generally work in one direction, so check whether there is a reverse pressure difference and, if so, install a check valve. When the fluid cleanliness is poor, install a filter before the solenoid valve - solenoid valves generally require good medium cleanliness. Note the flow orifice and pipe connection bore; solenoid valves generally provide only open/close two-position control; where conditions allow, install a bypass pipe for easy maintenance; where water hammer occurs, a solenoid valve with adjustable opening and closing times must be ordered. Note the effect of ambient temperature on the solenoid valve. The supply current and power consumption should be selected according to the output capacity; the supply voltage generally allows about ±10%, and note that the VA value is high when an AC coil starts.   

    2. Reliability: solenoid valves are divided into normally closed and normally open types; normally closed is generally chosen, opening when energised and closing when de-energised; but where the opening time is very long and the closing time very short, the normally open type should be chosen. Life testing is generally a type test item in factories; strictly speaking there is as yet no dedicated national standard for solenoid valves in China, so choose solenoid valve manufacturers carefully. Where the action time is very short and the frequency high, the direct-acting type is generally chosen, and for large bores the fast series.   

    3. Safety: ordinary solenoid valves are not water-tight; where conditions do not allow, choose a water-tight type, which factories can custom-make. The maximum rated nominal pressure of the solenoid valve must exceed the maximum pressure in the pipeline, otherwise the service life will be shortened or other unexpected situations will arise. For corrosive liquids choose the all-stainless-steel type, and for strongly corrosive fluids the PTFE (SLF) solenoid valve. In explosive atmospheres the corresponding explosion-proof product must be used.   

    4. Economy: many solenoid valves are interchangeable, but on the basis of meeting the above three points the most economical product should be chosen. [Edit this section] Selection of solenoid valves: selection should first follow, in order, the four principles of safety, reliability, suitability and economy, and then be based on six aspects of the site conditions (namely pipe parameters, fluid parameters, pressure parameters, electrical parameters, mode of action and special requirements).   


    Basis for selection:   
    1. Selecting the bore size (DN) and connection type from the pipe parameters: 1) determine the bore size (DN) from the actual pipe internal diameter or the flow requirement; 2) connection type - generally flanged connections are chosen for >DN50, while for ≤DN50 the user may choose freely as required.   

    2. Selecting the material and temperature class of the solenoid valve from the fluid parameters: 1) corrosive fluids: corrosion-resistant solenoid valves and all-stainless-steel types are preferable; for edible ultra-clean fluids, food-grade stainless steel solenoid valves are preferable.
      2) High-temperature fluids: choose solenoid valves made with high-temperature-resistant electrical and sealing materials, and choose the piston-type construction.
      3) Fluid state: broadly gaseous, liquid or mixed; this must be distinguished clearly, especially when ordering bores above DN25.
      4) Fluid viscosity: generally any type may be chosen below 50 cSt; above this value a high-viscosity solenoid valve should be used.   

    3. Selecting the principle and structural type of the solenoid valve from the pressure parameters
      1) Nominal pressure: this parameter has the same meaning as for other general valves and is determined by the nominal pressure of the pipeline.
      2) Working pressure: if the working pressure is low, the direct-acting or step direct-acting principle must be used; when the minimum working pressure difference is above 0.04 MPa, direct-acting, step direct-acting and pilot-operated types may all be used.   
    4. Electrical selection: AC 220 V and DC 24 V are the most convenient voltage ratings and should be given priority.   
    5. Selection according to the duration of continuous operation: normally closed, normally open, or capable of continuous energisation. 1) When the solenoid valve must stay open for a long time and the open time exceeds the closed time, the normally open type should be chosen.
     2) If the opening time is short, or the open and close times are not many, choose the normally closed type.
    3) However, in some safety protection duties, such as flame monitoring in furnaces and kilns, the normally open type must not be chosen; a type that can be energised continuously for long periods should be chosen.   
    6. Selecting auxiliary functions according to environmental requirements: explosion protection, non-return, manual operation, water and mist tightness, water spray tightness, submersible. 1) Explosive atmospheres: solenoid valves of the corresponding explosion protection grade must be used (our company offers d II BT4, d II CT5 and Ex m I/II T4).
      2) When reverse flow occurs in the pipeline, our OK71-N and OK72-N series solenoid valves with non-return function can be chosen.
       3) When on-site manual operation of the solenoid valve is needed, our OK71-S and OK72-S series with manual function can be chosen.
      4) For outdoor installation or dusty locations, choose water-tight and dust-tight types (ingress protection IP54 or better).
      5) For fountains, submersible solenoid valves must be used (ingress protection IP68 or better).
       Characteristics to note when selecting and using   
    1. Safety:
      1) Corrosive media: PTFE solenoid valves and all-stainless-steel types are preferable; for strongly corrosive media the isolated-diaphragm type must be used, e.g. CD-F, Z3CF. For neutral media, solenoid valves with a copper alloy valve shell are also preferable, otherwise rust flakes often fall off inside the shell, especially where operation is infrequent. Copper must not be used for ammonia valves.
      2) Explosive atmospheres: products of the corresponding explosion protection grade must be used; for outdoor installation or dusty locations, water-tight and dust-tight types should be used.
      3) The nominal pressure of the solenoid valve should exceed the maximum working pressure in the pipeline.    
    2. Suitability:
        1. Medium characteristics
      1.1 Choose different solenoid valve types for gaseous, liquid or mixed states, e.g. ZQDF for air, ZQDF-Y for liquids and ZQDF-2 (or -3) for steam, otherwise misoperation is likely. The ZDF series multi-function solenoid valve can be used for gas and liquid alike. It is best to state the medium state when ordering, so that the installing user need not adjust it again.
     1.2 Use products of the correct specification for the medium temperature, otherwise the coil will burn out and the seals will age, seriously affecting the service life.
    1.3 Medium viscosity, generally below 50 cSt. If above this value, for bores larger than 15 mm order the ZDF series multi-function solenoid valve as a special order; for bores smaller than 15 mm order a high-viscosity solenoid valve.
     1.4 When the medium cleanliness is poor, a back-flush filter valve should be fitted before the solenoid valve; where the pressure is low a direct-acting diaphragm solenoid valve such as CD-P can also be used.
    1.5 Where the medium flows in one fixed direction and reverse flow is not permitted, the ZDF-N and ZQDF-N require two-way flow, so state this as a special requirement.
     1.6 The medium temperature should be chosen within the permissible range of the solenoid valve.
     2. Pipe parameters
     2.1 Choose the valve port and model according to the medium flow direction requirement and the pipe connection method. For example, to switch one pipeline to two pipelines, choose CA5 and Z3F for small bores and ZDF-Z1/2 for medium or large bores; to control the merging of two pipelines, choose ZDF-Z2/1, etc.
     2.2 Determine the nominal bore from the flow rate and the valve Kv value, or use the pipe internal diameter. Note that some manufacturers do not state a Kv value and the valve port is often smaller than the connecting pipe bore - do not be misled by a low price.
     2.3 Working pressure difference: when the minimum working pressure difference is above 0.04 MPa, an indirect pilot-operated type may be used; when the minimum working pressure difference is close to or below zero, the direct-acting or step direct-acting type must be used.
      3. Environmental conditions
      3.1 The maximum and minimum ambient temperatures should be within the permissible range; if outside, a special order must be placed.
      3.2 Where relative humidity is high, or where there is dripping water or rain, choose a water-tight solenoid valve
      3.3 Where there is frequent vibration, shaking and impact, choose special types, for example marine solenoid valves.
      3.4 In corrosive or explosive atmospheres, priority should be given, in accordance with safety requirements, to corrosion-resistant types
      3.5 If space is restricted, choose the multi-function solenoid valve, since it dispenses with the bypass and three manual valves and is easy to service in line.
      4. Power supply conditions
      4.1 Choose AC or DC solenoid valves according to the type of power supply. Generally AC supply is more convenient.
      4.2 For voltage rating, give priority to AC 220 V and DC 24 V.
      4.3 Supply voltage fluctuation: for AC, typically +10% to -15%; for DC, about ±10%; if outside these limits, voltage stabilisation measures must be taken or a special order placed.
      4.4 The rated current and power consumption should be chosen according to the supply capacity. Note that the VA value is high when an AC coil starts; where capacity is insufficient, an indirect pilot-operated solenoid valve should be preferred.
      5. Control accuracy
      5.1 An ordinary solenoid valve has only the two positions open and closed; where control accuracy is high and stable parameters are required, choose a multi-position solenoid valve: the Z3CF three-position normally open solenoid valve offers three flows - cracking, fully open and closed - and the ZDF-Z1/1 combined multi-function solenoid valve offers four flows: fully open, large open, small open and fully open.
      5.2 Action time: the time from the electrical signal being made or broken to completion of the main valve action. Only our company's patented multi-function solenoid valve allows the opening and closing times to be adjusted separately, which both meets the control accuracy requirement and prevents water hammer damage.
      5.3 Leakage: the leakage values given in the catalogue are the usual economical grade; if these are considered too high, place a special order.   
     3. Reliability:
      1) Service life: this is not an ex-works test item but a type test item. To ensure quality, choose branded products from reputable manufacturers.
      2) Duty: there are three types - continuous duty, repeated short-time duty and short-time duty. Our standard products are all continuous duty, i.e. the coil may be energised continuously for long periods. Where the valve is open for a long time and closed only briefly, a normally open solenoid valve should be chosen. Where short-time duty is used and quantities are large, a special order can be placed to reduce power consumption.
      3) Operating frequency: where a high action frequency is required, the direct-acting construction should be preferred and AC supply chosen.
      4) Operating reliability: strictly speaking this test has not yet been formally included in China's dedicated standard for solenoid valves; to ensure quality choose branded products from reputable manufacturers. In some applications the number of operations is small but the reliability requirement is very high, such as fire protection and emergency protection, and this must not be treated lightly. In particularly important cases two valves should be used in series for double insurance.    
    4. Economy: this is one criterion for selection, but the economy must be on the basis of safety, suitability and reliability. Economy is not only the purchase price; the function and quality of the product and the cost of installation, maintenance and other accessories must be given priority. More importantly, the cost of a single solenoid valve in the whole automatic control system and even in the production line is negligible, so false economy in selection can cause enormous losses.
    Sealing materials for solenoid valves: NBR / EPDM / VITON fluoroelastomer (FKM)

Use of solenoid valves
    Installation notes:
    1) When installing, note that the arrow on the valve body must agree with the direction of medium flow. Do not install where water drips or splashes directly. The solenoid valve should be installed vertically upwards.   
    2) The solenoid valve must work reliably with the supply voltage varying within 15% to 10% of the rated voltage.  
    3) After installation there must be no reverse pressure difference in the pipeline. Energise it several times and let it reach normal temperature before putting it into formal service.   
    4) Clean the pipeline thoroughly before installing the solenoid valve. The medium introduced must be free from impurities. Fit a filter before the valve.   
    5) When the solenoid valve fails or is being cleaned, a bypass arrangement should be installed so that the system can keep running.
    Applications of solenoid valves: solenoid valves are used for on/off control of liquid and gas pipelines and are two-position DO control. They are generally used for the control of small pipelines.   
    Solenoid valves can only be used for on/off duty, i.e. DO control, and only for small pipeline control, commonly for DN50 and below; above this they are rarely used.   
    1. Switching form: a solenoid valve is driven by a coil and can only open or close, with a short action time when switching.   
    2. Working characteristics: a solenoid valve generally has a very small flow coefficient and a very small working pressure difference. For example, a 25 mm solenoid valve has a much smaller flow coefficient than a 15 mm electric ball valve. The solenoid valve is driven by a solenoid coil and is relatively easily damaged by voltage surges. It acts as a switch, with just the two functions of opening and closing.  
    A solenoid valve generally resets when de-energised; an electric valve needs a reset device to provide this function.


    Common faults of solenoid valves:
    ■ Solenoid valve coil burnt out, generally caused by moisture and water ingress
    ■ Solenoid valve stuck, with impurities entering.
    ■ Solenoid valve leaking, generally due to a damaged gasket or a worn spool
    1. Solenoid valve does not work after energising. Check whether the power connection is poor → rewire and check the plug connection. Check whether the supply voltage is within the working range → adjust to the normal range. Check whether the coil is unsoldered → resolder. Check for a short-circuited coil → replace the coil. Check whether the working pressure difference is unsuitable → adjust the pressure difference → or replace with a matching solenoid valve. Check whether the fluid temperature is too high → replace with a matching solenoid valve. Check whether impurities have jammed the main spool and movable core → clean; if the seal is damaged, replace the seal and install a filter. Check whether the liquid viscosity is too high, the frequency too high or the life expired → replace the product
    2. Solenoid valve will not close. The seal of the main spool or movable core is damaged → replace the seal. Check whether the fluid temperature or viscosity is too high → replace with a suitable solenoid valve. Check whether impurities have entered the valve spool or movable core → clean. Check whether the spring life has expired or the spring is deformed → replace. Check whether the throttle or balance orifice is blocked → clean in good time. Check whether the working frequency is too high or the life expired → choose another product or replace it
    3. Other cases. Internal leakage → check whether the seal is damaged and whether the spring is badly assembled. External leakage → loose connection or damaged seal → tighten the screws or replace the seal. Noise when energised → fasteners on the head are loose, tighten them; voltage fluctuation outside the permitted range, adjust the voltage; impurities on the core mating face or an uneven surface, clean or replace in good time.