Typical fluid flow velocities




The concept of the flow coefficient and its calculation
    A control valve, like an orifice plate, is a local resistance element. The former is a variable throttling element because its throttling area can be changed by the movement of the valve plug; the latter differs only in that its bore cannot change.
    However, we can model the control valve as orifice-plate throttling, as shown in Fig. 2-1. For an incompressible fluid, substituting into Bernoulli's equation gives:
    Solving gives Let Then, combining the continuity equation Q = AV with the formula above and solving together gives: V1, V2 - velocities before and after throttling;
    V - mean flow velocity;
    P1, P2 - pressures before and after throttling, 100 kPa;
    A - throttling area, cm ;
    Q - flow rate, cm/S;
    ξ - resistance coefficient;
    r - specific weight, kgf/cm;
    g - acceleration, g = 981 cm/s  ;
    If Q, P1, P2 and r above are expressed in engineering units, i.e. Q in m/ h;P1 、P2 —— 100KPa; r——gf/cm. Then formula (2) becomes:

       

    Then let the coefficient of the flow rate Qbe Kv, i.e. Kv = 
         
    This is where the flow coefficient Kv comes from. It can be seen that the greater the resistance of the valve the smaller the Kv value, and the larger the bore the larger the Kv.   Flow coefficient formulas for compressible fluids
    Compressible fluids have different calculation formulas depending on the approach taken; the two mainly used are the compressibility factor method and the mean specific weight method.
    The compressibility factor method multiplies the flow coefficient formula (4) for incompressible fluids by a compressibility factorεwhich gives

       

    where,ε- compressibility factor, determined experimentally asε=  1 - 0.46 ΔP/P1, at
    saturated conditions, ΔP/P1 = 0.5, at which the flow no longer increases with ΔP
    but chokes flow (choked flow is defined as:
    the maximum limiting flow state reached when fluid passes through a control valve),

      Pressure recovery factor FL
    In the derivation of the original formula from P1 it is assumed that at the throttling point of the control valve the pressure falls directly from P1 to P2, as shown by the dashed line in Fig. 2-3. In reality, however, the pressure curve is as shown by the solid line in Fig. 2-3: pressure recovery occurs. Different valve constructions recover pressure differently. The lower the resistance of the valve, the greater the recovery, the more the pressure curve departs from that assumed in the original derivation, and the greater the error between the calculated and actual results. A coefficient FL representing the degree of pressure recovery of the valve is therefore introduced to correct the original formula. FL is called the pressure recovery factor, and its expression is:       (9)
    where and denote the pressure difference at the vena contracta when flashing occurs and the pressure difference across the valve.  
    Fig. 2-3 Pressure recovery within the valve The key point is the experimental determination of FL. Testing with a transparent valve body shows that once flashing occurs at the throttling point, i.e. once a cluster of bubbles forms there, Q essentially stops increasing with ΔP. This test shows that:
    the critical pressure difference for flashing is the critical pressure difference for choked flow, so FL is also called the critical flow factor. FL can therefore represent the pressure recovery caused by different valve constructions,
    and so correct the flow coefficient calculation error caused by different valve constructions, and can also be used to distinguish normal flow from choked flow, i.e. the pressure difference ΔPc in the defining formula (9) for FL is the critical pressure difference at which the test valve becomes choked.
    Thus, when ΔP < ΔPc the flow is normal, and when ΔP ≥ ΔPc the flow is choked.  

    Control valve type

    Flow direction

    FL value


    Single-seat



    Plunger-type plug

    flow-to-open

    0.90

    flow-to-close

    0.80

    "V"-port plug

    any flow direction

    0.90

    Cage-type plug

    flow-to-open

    0.90

    flow-to-close

    0.80


    Plunger-type plug

    any flow direction

    0.85

    "V"-port plug

    any flow direction

    0.90

    Angle control valve

    Plunger-type plug

    flow-to-open

    0.80

    flow-to-close

    0.90

    Cage-type plug

    flow-to-open

    0.85

    flow-to-close

    0.80

    Venturi type

    flow-to-close

    0.50

    Ball valves

    "O" port

    any flow direction

    0.55

    "V" port

    any flow direction

    0.57

    Butterfly valve

    60° full open

    any flow direction

    0.68

    90° full open

    any flow direction

    0.55

    Eccentric rotary valve

     

    flow-to-open

    0.85

       
Flow characteristic


Relative flow% \ relative travel% 0 10 20 30 40 50 60 70 80 90 100
Linear flow characteristic (1) 3.3 13.0 22.7 32.3 42.0 51.7 61.3 71.0 80.6 90.3 100
Equal-percentage flow characteristic (2) 3.3 4.67 6.58 9.26 13.0 18.3 25.6 36.2 50.8 71.2 100
Quick-opening flow characteristic (3) 3.3 21.7 38.1 52.6 65.2 75.8 84.5 91.3 96.13 99.03 100
Parabolic flow characteristic 3.3 7.3 12 18 26 35 45 57 70 84 100
Cv and Kv
    Cv calculation formula. When sizing a control valve, the required Cv value (Kv value) should first be calculated from the known fluid conditions, and a suitable valve size is then selected from the rated Cv value tables in the control valve selection catalogue.
    The most widely used Cv calculation formula is that laid down by the FCI. Its details are as follows:
    1. Definition of the Cv value
    Definition of Cv: the number of US gallons per minute of clean water at 60°F (15.6°C) that flows through the valve when it is fully open with a pressure difference of 1 pound/inch2 (0.07 kgf/cm2) across it (Cv = 1.17 Kv, where Kv is the symbol used in our country for the flow coefficient of control valves)
    Kv is defined as: when the control valve is fully open, the pressure difference ΔP across the valve is 100 kPa and the specific weight r of the fluid is 1 kgf/cm3 (i.e. water at normal temperature), the flow rate passing through the control valve per hour.

Online Cv calculation for gases and liquids

Download Cv calculation software