Performance testing of control valves

    The performance indices of a pneumatic control valve are: basic error, hysteresis, dead band, start and end point deviation, rated travel deviation, leakage, tightness, pressure resistance, appearance, rated flow coefficient, inherent flow characteristic, vibration resistance and operating life - 13 items in all, of which the first 9 are ex-works test items. Because of factors such as transport of the valve and adjustment of the working spring range, the following performance items often have to be adjusted and checked before installation:


    1) Basic error
    Feed the specified input signal smoothly to the actuator air chamber (or positioner) in the increasing and decreasing directions, measure the corresponding travel value at each point, and calculate the error at each point between the actual "signal-travel" relationship and the theoretical relationship. Its maximum value is the basic error. The test points should at least include 0, 25%, 50%, 75% and 100% of the signal range. The basic error limit of the measuring instrument should be less than one quarter of the basic error limit of the valve under test.
    2) Hysteresis
    The test procedure is the same as in item 1) above. The maximum difference between the upscale and downscale travel measured at the same input signal is the hysteresis.
    3) Start and end point deviation
    The method is the same as in item 1). The basic error at the upper limit (start point) of the signal is the start point deviation; the basic error at the lower limit (end point) of the signal is the end point deviation.
    4) Rated travel deviation
    Apply the rated input signal to the pneumatic actuator air chamber (or positioner) so that the stem makes the full stroke; the ratio of the difference between actual travel and rated travel to the rated travel is the rated travel deviation. The actual travel must be greater than the rated travel.
    5) Leakage
    The test medium is clean gas (air or nitrogen) or liquid (water or kerosene) at 10-50 °C. Test procedure A: when the permissible differential pressure of the valve is above 350 kPa the test pressure is 350 kPa, and when it is below 350 kPa the test pressure is the permissible differential pressure; procedure B uses the maximum working differential pressure of the valve. The test signal pressure must ensure that the valve is closed. In procedure A, the signal pressure to the actuator of an air-to-open valve is zero, and for an air-to-close valve it is the upper limit of the input signal plus 20 kPa; for a two-position valve the actuator signal pressure should be the design value. In procedure B the actuator signal pressure should be the design value. The test medium should be introduced into the valve in the specified flow direction; the valve outlet may be open directly to atmosphere or connected to a low-pressure-loss measuring device open to atmosphere, and leakage may be measured only after the valve and all downstream piping are confirmed to be completely full of medium.



    Main performance and testing of electric control valves

    The main performance indices of an electric control valve are: basic error, hysteresis, dead band, rated travel deviation, leakage, tightness, pressure resistance, appearance, rated flow coefficient, inherent flow characteristic, vibration resistance, temperature, long-term operating reliability, explosion protection, damping characteristic, effect of supply voltage variation, effect of ambient temperature variation, insulation resistance and dielectric strength. The requirements and test methods for the first 10 items are the same as or similar to those for pneumatic valves; of these, basic error, hysteresis, dead band, leakage, tightness, appearance, damping characteristic, effect of supply voltage variation and insulation resistance are ex-works test items. The requirements and test methods for the last 3 performance indices are as follows:


    1) Damping characteristic
    The damping characteristic of an electric control valve is specified as no more than 3 "half-cycle" swings of the stem in each of the upscale and downscale directions. The test method is to apply input signals of 20%, 50% and 80% of the input signal range at the input and observe the number of "half-cycle" swings of the stem at the corresponding positions in the upscale and downscale directions.
    2) Effect of supply voltage variation
    When the supply voltage of the electric control valve varies within 220 +20/-30 V, the change in stem displacement should not exceed 1.5% of the full stroke. The test method is: with the supply voltage at 220 V, apply a signal of 20% of the signal range at the input and measure the corresponding stem travel; then set the supply voltage to 190 V and 240 V and measure the corresponding change in stem travel. Repeat with signals of 50% and 80% of the signal range and measure the change in stem travel.
    3) Insulation resistance
    When the ambient temperature is 10-35 °C and the relative humidity does not exceed 85%, the insulation resistance of the electric control valve should meet the following requirements: not less than 20 MΩ from each input terminal to the enclosure; not less than 50 MΩ from each input terminal to the supply terminals; not less than 50 MΩ from the supply terminals to the enclosure. The test method is to use a type 500 megohmmeter.


Inspection of control valves

    The control valve body is in direct contact with the process medium, and its performance directly affects system quality and environmental pollution, so pneumatic control valves must be maintained regularly and overhauled periodically; in severe duty and important applications, maintenance work deserves even more attention.
    Key inspection points
    1) Inner wall of the valve body
    For control valves used with high differential pressures and corrosive media, the inner wall of the body and the diaphragm of diaphragm valves are constantly subjected to impact and corrosion by the medium, so their pressure resistance and corrosion resistance must be inspected closely.
    2) Seat
    During operation, medium infiltration can corrode the internal thread surface that secures the seat, loosening the seat, and care should be taken to check this. For valves working at high differential pressures, also check whether the seat sealing face has been eroded.
    3) Plug
    The plug is the moving part of the control valve during operation and suffers the most severe erosion and corrosion by the medium, so during overhaul carefully check whether every part of the plug is corroded or worn, especially at high differential pressures where plug wear is more severe (because of cavitation). If the plug is badly damaged it should be replaced; also check whether the stem shows similar problems or has worked loose from the plug.
    4) Diaphragm, "O" rings and other gaskets.
    Check whether the diaphragm, "O" sealing rings and other gaskets in the control valve are aged or cracked.
    5) Packing
    Check whether the PTFE packing and the sealing grease are aged and whether the mating surfaces are damaged, and replace them when necessary.

Troubleshooting control valves

       

     

    Fault

    Cause

    Solution

    External leakage of the control valve

    1. Packing gland not tightened

    2. PTFE packing aged and deteriorated

    3. Damaged gasket, or loose hex nuts between the body and the upper/lower bonnet

     

    1. Add packing. To improve the sealing of the packing against the stem, more packing can be added, for example using a two-layer or multi-layer mixed packing arrangement. Merely increasing the number, e.g. from 3 rings to 5 rings, usually gives no obvious improvement.

    2. Replace the PTFE packing with graphite packing. The widely used PTFE packing works over -40 to 250 °C, and when the temperature varies over a wide range its sealing performance drops markedly, it ages quickly and its life is short. Flexible graphite packing overcomes these shortcomings and has a long service life. However, flexible graphite has large hysteresis and shows creep at first use, which must be taken into account. For control valves that use no sealing grease, adding sealing grease can be considered to improve stem sealing.

    3. Change the flow direction so that P2 is at the stem end. When ΔP is large and P1 is also large, sealing against P1 is clearly more difficult than sealing against P2. The flow direction can therefore be reversed, changing from P1 at the stem end to P2 at the stem end, which is effective for valves with high pressure and large differential pressure.

    4. Replace the gasket. At present most gaskets are still asbestos board, which has poor sealing performance at high temperature and a short life, causing leakage. In such cases spiral-wound gaskets, O-rings and the like can be used instead.

    Internal leakage of the control valve

     

     

    1. Plug or seat corroded or worn

    2. The thread on the outer ring of the seat corroded

    3. Large medium differential pressure and insufficient actuator output

    4. Foreign matter inside the valve body

     

    Solutions for valve leakage

    1. Choose suitable trim (plug, seat, stem); where requirements are higher, 1Cr18Ni9Ti or other stainless steel can be used. In severe flashing and cavitation duties, choose 1Cr18Ni9Ti with surface hardening - spraying or hardfacing a layer of cobalt-chromium-tungsten cemented carbide - or a solid cemented carbide plug. In strongly corrosive media, nickel alloys, titanium and non-metallic materials can be used; commonly used nickel alloys include Monel (nickel-copper alloy, alkali-resistant, suitable for hydrofluoric acid), Hastelloy B (nickel-molybdenum alloy, alkali-resistant, suitable for hydrochloric, sulphuric and nitric acids), Hastelloy C (nickel-molybdenum-chromium alloy, suitable for dilute hydrochloric and nitric acid aqueous solutions at room temperature) and Inconel (a high-temperature alloy).

    2. Reduce cavitation erosion of the trim. The main methods are: a) maintain sufficient downstream pressure, above the vapour pressure of the liquid, thereby preventing bubbles from forming in the low-pressure high-velocity region; this is usually done by fitting anti-cavitation trim in the valve. b) Choose flow-to-close valves; in high-pressure angle valves with downward flow, use a sharp-edged seat orifice so that the discharge is kept away from the inner wall of the body. Crushing the bubbles in the flowing stream is less harmful than crushing them in a rapidly expanding seat orifice and on the body inner wall. If this cannot be achieved, a gradually expanding seat orifice can be used. c) Limit the valve pressure drop by using two valves in series with the pressure drop shared between them; the pressure drop in the upstream valve may be larger.

    3. Lap the sealing face to improve surface finish, reducing or eliminating the sealing clearance.

    4. Change from flow-to-open to flow-to-close. In a flow-to-close valve the unbalanced force tends to close the plug, giving a good sealing effect.

    5. Increase the actuator output force. This is a common way of improving sealing performance. Usual measures are shifting the spring working range, using a lower-stiffness spring, adding a positioner, raising the air supply
    pressure, and changing to an actuator with greater thrust.

    6. Dismantle the valve and clean out debris. For small-bore control valves, especially micro-flow control valves with small throttling clearances, a pipeline filter can be installed before the control valve.

    7. Change to another type of control valve. Because the inverted S-shaped flow path of a straight-through valve has many dead zones in the cavity, straight-through single-seat and double-seat valves can be changed to cage valves with window-type throttling areas, or to angle valves whose inverted L flow path gives good self-cleaning performance.

    Control valve vibration
    accompanied by noise

    1. There is a vibration source near the control valve whose frequency equals or is close to the natural frequency of the valve.

    2. Cavitation noise from the collapse of cavitation bubbles in the fluid.

    3. Noise produced when compressible fluid passes through the control valve at a velocity equal to or above sonic velocity.

     

    1. Remove the vibration sources near the control valve. If the source cannot be removed, the following measures can be taken: for slight resonance, increase the stiffness of the valve (e.g. use a stiffer spring or change to a piston actuator) and add damping; for moderate resonance, change the shape of the throttling part or replace it; for severe resonance, change the throttling type of the control valve, e.g. change a double-seat valve to a cage valve or a cage valve to a double-seat valve (valves of different construction have different natural frequencies, and changing the valve type is the most effective way of eliminating resonance at its root); if the piping or foundation vibrates severely, add supports to eliminate the vibration interference.

    2. Since cavitation noise accompanies flashing and cavitation of the fluid, the measures for cavitation noise are the same as those for reducing flashing and cavitation, as follows:
    a) use special trim with staged or multi-stage pressure reduction, design the fluid passages of the body sensibly and avoid as far as possible the fluid impinging perpendicularly on the trim and the cavity;
    b) control the medium velocity and reduce the working differential pressure so that the velocity slows, but if the differential pressure across the control valve is too large and the valve opening too small, the velocity at the throttle will increase and the pressure drop rapidly, so this method is relative in nature and its effect is not ideal;
    c) enlarge the valve outlet, although this is not very advisable from the point of view of economy and practicality;
    d) use hardened trim to increase the surface hardness of the valve internals.

    3. Choose a low-noise control valve, so that the fluid is throttled through a tortuous path and decelerated gradually, avoiding velocities above sonic velocity.

    4. Use a perforated restriction plate or diffuser to absorb part of the pressure drop downstream of the valve, thereby raising the downstream pressure and reducing the throttling velocity, so lowering the noise.

    5. Change the piping downstream of the control valve to thick-wall pipe, or use sound-insulating material to isolate the noise. This method is only applicable where the noise is not very high and the pipeline is not very long.

    6. Use a silencer to absorb noise and reduce its propagation.

    Causes of a control valve not operating

    1. Controller fault, so that the control valve receives no electrical signal.

    2. Leak in the air supply main, so that the valve positioner has no air supply or insufficient air supply pressure.

    3. Leaking bellows in the positioner, so that the positioner has no air output.

    4. Damaged diaphragm in the control valve.

    5. The fixed orifice of the amplifier in the positioner is blocked, or the compressed air contains water that accumulates at the amplifier ball valve, so that the positioner has an air supply but no output.

    1. Replace the faulty controller;

    2. Find the leak and replace the air supply main;

    3. Replace the leaking bellows;

    4. Replace the diaphragm in the diaphragm case;

    5. Clear the fixed orifice of the amplifier and add air supply filtration and dehydration.

    Unstable control valve output
    causing oscillation

    1. Unstable output signal from the controller;

    2. Severe vibration of the piping or foundation;

    3. Excessive sensitivity of the valve positioner;

    4. Flow coefficient C selected too large, so that the control valve works at a small opening;

    5. Excessive clearance in the fit and guidance of the throttling part;

    6. High stem friction, which readily produces hysteresis oscillation;

    7. Insufficient actuator stiffness, causing oscillation over the full stroke, or insufficient spring preload, causing oscillation at low travel.

    1. Change the direction of action of the unbalanced force Ft. This is usually done by changing the flow direction.

    2. Avoid the valve's own unstable region. The valve readily oscillates where the direction of the unbalanced force changes. For example, a double-seat valve generally changes
    at openings within 10% and between 100% and 90%, which should be avoided as far as possible in service.

    3. Change to a valve with better stability. A stable valve has a smaller change in unbalanced force and good guidance. Where a single-seat or double-seat valve is insufficiently stable, a cage valve can be used instead.

    4. Increase spring stiffness. This is a common way of improving stability, e.g. changing a 20-100 kPa spring to a 60-180 kPa high-stiffness spring, and fitting a positioner to valves that have none.

    5. Reduce the response speed. Where the system requires the valve response or regulating speed not to be too fast while the valve is fast, or where the system itself is a fast-response system and the valve is fitted with a positioner
    to speed up its action, overshoot and oscillation will occur.

    Valve positioner
    Common faults

    1. Signal present but no output: the fixed orifice of the amplifier is blocked; the nozzle and back-pressure pipe are blocked by dirt, so the back pressure is at its maximum;

    2. No signal but output present: the amplifier ball valve is stuck; the nozzle and flapper do not close tightly;

    3. Output pressure slow or abnormal: the moving parts are stuck, so there is no feedback force; the amplifier ball valve does not close tightly; the output or input piping leaks; the diaphragm case leaks.

    1. Check and clean the fixed orifice, nozzle and back-pressure piping;

    2. Check and clean the amplifier and adjust the nozzle position

    3. Remove the cause of sticking, add lubrication, clean the amplifier, check the air circuit for tightness and replace the diaphragm.

Installation of control valves
    Control valve installation

    When installing a control valve, note the following points:
    Checking the control valve before installation; the safety of personnel and equipment during all stages of valve handling, i.e. installation, testing, operation and maintenance; the performance of the control valve as the final control element in the control loop; where manual operation is required, the installation requirements for effective manual operation of the system; accessibility of the control valve for maintenance; maintenance, operating and installation costs; protective measures forced on the valve by mechanical or environmental requirements.

     

    1 Inspection before installation

    When the control valve arrives on site it should be inspected immediately to confirm that it meets the specification, particularly installation dimensions, materials and accessories. At this stage any obvious mechanical damage caused during transport and handling should be dealt with promptly. To ensure that the control valve operates correctly at start-up and that the system runs safely, the following items should also be checked:
    (1) Visual inspection

    (2) Start and end point deviation
    (3) Full stroke deviation

    (4) Basic error
    (5) Upscale and downscale travel deviation

    (6) Leakage
    (7) Operational check of all auxiliary equipment such as limit switches and valve positioners.

    2 Safety considerations

    When designing and installing the piping for the valve, the following problems and their solutions must all be considered:

    (1) The valve may leak - whether at the start of service or during operation - at the packing gland cover, at flange gaskets, or at pinholes formed when the valve is damaged. If liquid flows through the valve under very severe operating conditions (temperature and pressure) this may damage the valve; corrosive fluids may collect in cable trenches, flammable fluids may fall into hot vessels, and hot alkaline solutions may injure operating personnel.
    (2) After isolation, system pressure can remain in the valve for a time; if the valve is to be opened or removed for repair there must be a safe means of relieving this pressure. There must likewise be a means of draining accumulated hazardous liquids.
    (3) A large quantity of high-pressure fluid trapped between isolating valves can represent considerable stored energy, and carelessness when relieving pressure at the control valve can cause serious injury or death.
    (4) It must be assumed that even a good design will inevitably trap high-pressure fluid when isolated, so it is recommended that where the potential energy of the trapped liquid is very hazardous, vent and/or drain valves be installed on each side of the control valve.
    (5) For valves in which a large quantity of high-pressure material accumulates, it is necessary to consider installing two vent and drain valves. Only a small quantity of material accumulates between the two valves, and the system pressure can be released gradually, so that pressure between the two drain or vent valves is repeatedly built up and released. Note that during this process the control valve must be open.
    (6) If the fluid being relieved is a hazardous gas, the vent line must be routed to a safe location.
    (7) Even if the gas is not flammable, a vent line is still needed so that the gas blown off does not carry rust or other material that could injure the person handling the vent valve.
    (8) Choose a vent valve that limits the flow, so protecting careless operators who fail to follow the safe practice of opening the vent valve slowly. If the fluid contains suspended solids, such a restricted-flow vent valve is easily blocked. Venting may therefore have to be done through large-size drain valves on valves installed at the top of the pipeline. In this connection, training personnel to operate restricted-flow vent valves safely is very important. If the fluid discharged is a hazardous liquid, the piping designer must consider routing the discharge line to a safe location. During plant operation the valve may be very hot, so precautions must be taken to prevent burns to operators.
    (9) When preparing threaded pipe joints, take care to prevent pipe sealant from getting into the installed pipeline. Use pipe sealant sparingly and leave the first two threads uncoated; PTFE tape can also be used as the thread sealant
    (10) For steam lines, insulation should be provided close to the upstream or downstream of the control valve.
    (11) Where pressure fluctuations are severe, a pipeline damper (snubber) is recommended.

    3 Consideration of control valve performance

    When designing the inlet and outlet piping of a control valve, it is prudent to treat the control valve as a variable orifice plate. Recommendations for the piping of a pipe/orifice assembly are as follows:
    (1) Make the inlet piping as long a straight run as possible, consistent with other piping requirements. As a rule of thumb the straight length is 10 to 20 pipe diameters. This is easy for small pipelines, but generally impossible for pipelines with a nominal bore above 125 mm. However, the longer the straight inlet run, the better the valve performance obtained.
    (2) Where possible the outlet piping should have a straight run of 3 to 5 pipe diameters.
    (3) The inlet straight run allows the fluid to enter the valve at a steady pressure. Thus at every valve position - in other words, for every new orifice opening - the steady inlet pressure guarantees a steady, repeatable flow. Fig. 7-1 shows a good flow arrangement, while Fig. 7-2 shows a poor one.

     

    Fig. 1 Typical good arrangement of upstream and downstream piping

     

    Fig. 2 Poor arrangement of upstream and downstream piping

     

    Fig. 3 Common bypass arrangements for control valves

    (4) Note the position of the pressure gauge in Fig. 7-1: at that position the gauge indicates a steady, true pressure rather than the pressure head plus or minus the velocity head caused by a non-uniform flow profile. Accurate measurement of upstream and downstream pressure is in fact particularly important when investigating fluid system faults. Correct measurement of the pressure drop across the control valve, together with observation of the valve position, shows whether the valve is operating as designed or whether it needs to be isolated and repaired because of an internal fault.
    (5) The location of the upstream or downstream pressure tapping points of a pressure-regulating valve must follow the above recommendations, to ensure measurement accuracy and steady pressure unaffected by fittings.

    4 Consideration of manual operation

    The installation position of the control valve should take the following factors into account so as to facilitate manual operation:
    (1) Is the valve installed where the operator can conveniently operate it by hand, and at the same time see the parameters shown on the indicator while operating it?
    (2) If the level is to be controlled manually, can the operator see the glass level gauge on the tank?
    (3) Can the operator determine the amount of stem movement by observing the pressure gauge on the pipeline or the stem travel indicator?
    (4) Can indicators of other parameters enable the operator to anticipate changes in parameters? For example, an operator regulating boiler feedwater flow: can he observe the steam pressure gauge directly and, according to the increase or decrease of steam flow indicated by the steam pressure gauge or flow meter, adjust the required feedwater flow in advance.
    (5) If a bypass valve is to be used for manual operation, the bypass valve should be selected with the same flow characteristic and travel as the control valve.
    (6) For pneumatic control valves without a handwheel, or with a handwheel but in important control systems, manual bypass and isolation valves may be adopted as appropriate, with isolating valves and a bypass valve installed. There are many bypass arrangements; the four commonly used ones (see Fig. 7-3) are compared here.
    (a) Arrangement a: this is the arrangement traditionally used; the bypass can be used for automatic venting/control, but as the two isolating valves are on the same pipeline as the control valve it is difficult to dismantle and install, and it takes up a lot of space.
    (b) Arrangement b: this arrangement is better, being compact, occupying little space and easy to dismantle.
    (c) Arrangement c: this arrangement is also fairly good and easy to dismantle, but it occupies slightly more space than arrangement (b).
    (d) Arrangement d: this arrangement is only suitable for small-bore control valves, otherwise the actuator is mounted too high and is inconvenient to install and remove.

    5 Consideration of accessibility

    When installing a control valve, the possibility of on-site repair or scheduled dismantling must be considered. Maintenance costs depend to a large extent on the accessibility of the valve, especially for valves at height. Some piping designs are barely accessible even to maintenance personnel
    - how then can they be properly installed and maintained? At the same time the space needed for control valve maintenance must be considered:
    (1) Space should be left above valves from which the top assembly with the stem and plug has to be removed;
    (2) Space should be left below the valve if the bottom flange and the stem and plug assembly are to be removed;
    (3) Space should be left at the side of the valve when removing valve accessories such as hand operators, actuators, solenoid valves and valve positioners;
    (4) Space should be left to facilitate removal of the bolts on the body flange. This dimension is often not provided, and designers must take it into account when designing the reducers connecting the inlet and outlet piping of the control valve. For large-bore valves, especially valves on elevated piping, ignoring this can cause very great difficulty in installing and removing the valve during maintenance. When maintaining a large-bore elevated valve in an imported plant, a whole week was needed just to remove the valve; the problem was that the space for removing it was too small.

    6 Consideration of installation cost

    Many factors must be considered in the piping design for a control valve. The basic requirement of these factors is that over the service life of the control valve the total cost is minimised while performance is the best. It is therefore useful to give careful consideration to the following series of questions, from the point of view of the economy and use of the control valve:
    (1) How should the inlet and outlet piping of the valve be designed?
    (2) How long should the straight runs be?
    (3) What pipeline size should be used?
    The piping design for the control valve must start with the overall piping design. Piping design generally has to satisfy pressure code requirements, corrosion and erosion requirements, noise level requirements and plant expansion requirements. The following fluid velocities are typical: liquid FH 1.5 m/s, steam 30 to 37.5 m/s, gas 70 to 120 m/s.
    The price of the pipe material and the fabrication cost have a great influence on the choice of pipeline size. High-pressure stainless steel piping systems require welding, stress relief and radiographic examination, which allows higher pipeline velocities to be chosen. According to the literature, steam velocities in high-pressure high-temperature service exceed 120 m/s, and feedwater velocities are 12 m/s.
    (4) Are reducers needed? Does the downstream piping have to be enlarged to accommodate the expansion of the fluid?
    (5) Are isolating valves needed? If so, what type and what size?
    (6) Is a bypass valve needed? If so, what type and what size?
    (7) Where in the pipeline relative to the sensing element should the control valve be installed?
    (8) At what height should the control valve be installed so that it is convenient for the operator?
    (9) Is the installed position of the control valve accessible for maintenance and manual operation? Can the stem travel indicator be seen during normal operation?
    (10) Is the control valve close to the equipment or indicators needed for manual operation?
    (11) Could it injure personnel or damage equipment at any stage of control valve operation?
    (12) Are vent and drain valves needed? If so, how many, of what type, what size, and where installed? Does the piping for these valves need to be routed to a safe location?
    (13) Are pressure gauges needed? If so, how many, where installed, and how piped?
    (14) Is a pressure relief device needed? If so, what size and where installed?
    (15) Is a pipeline filter needed? If so, is it fitted when the plant is built, or after the plant has been shut down and out of service awaiting repair?
    (16) What type of fittings are needed?
    (17) What construction materials should be used?
    (18) What code must the installed piping satisfy?
    (19) Does the valve need insulation?
    (20) Does the valve need a heat tracing line?
    (21) If the control valve cannot be installed vertically, what orientation should be chosen?
    (22) How should the control valve be supported?
    (23) What are the requirements for the pneumatic and hydraulic lines and auxiliary equipment?
    (24) If the control valve has been removed, how can the pneumatic or hydraulic piping and auxiliary equipment be isolated? Do the piping and auxiliary equipment need separate support? The same considerations must apply to the electrical equipment associated with electric control valves
    (25) Is a steam trap needed? If so, where installed?
    (26) Are pressure tapping nozzles needed? If so, where will the tapping points be, how large should the tapping valve be, and of what type?
    (27) Could the control valve be damaged by vehicles? If so, how will it be protected?
    (28) What anti-vibration and fire protection measures are there?
    (29) Is the valve reduced in bore, or are reducers used?
    In many cases the pipeline is chosen larger to accommodate future plant expansion. The control valve in a new plant can then be one or two sizes smaller than the pipeline in which it is installed. In this case there are two ways of selecting the control valve:
    ① Select a control valve of the same size as the pipeline and use small-diameter trim, e.g. dg50 trim in a DN100 valve;

    ② Select the smallest control valve obtained from the calculation and connect it to the pipeline with reducers.
    Which method to choose is generally decided by a cost analysis of the valve, the piping and the requirements. Pressure drop affects pump and power costs.
    The method of using a control valve of the same size as the pipeline with small trim is recommended. Unless the cost analysis shows that the smallest-diameter control valve has a great advantage, it is customary in many industrial processes to choose a control valve of the same size as the pipeline for DN50 and smaller lines.
    (30) Recommended sizes for isolating and bypass valves
    In many industrial processes it is common practice to install isolating valves and a bypass valve to suit the need for continuous operation of the equipment. The isolating valves are used to isolate the control valve, and the bypass valve is used while the control valve is being maintained.
    There are also exceptions where isolating valves are not used, since adding one or more isolating valves adds their cost: some process piping may need only one isolating valve to perform the whole function of isolating the control valve for maintenance. Some important processes cannot tolerate careless opening of the bypass valve or closing of the isolating valve.
    In most cases, taking cost into account, the minimum isolating and bypass valve sizes similar to those recommended in Table 7-1 are used.

     

    Table 7-1 Recommended minimum isolating and bypass valve sizes

     

    Pipeline size (in)

    1/2

    3/4

    1

    1 1/2

    2

    3

    4

    6

    8

    10

    12

    Control valve size (in)

    Isolating and bypass valve

    Isolating and bypass valve

    Isolating and bypass valve

    Isolating and bypass valve

    Isolating and bypass valve

    Isolating and bypass valve

    Isolating and bypass valve

    Isolating and bypass valve

    Isolating and bypass valve

    Isolating and bypass valve

    Isolating and bypass valve

    1/2

    1/2   1/2

    3/4   3/4

    1 1

    1 1/2   1 1/2

     

     

     

     

     

     

     

    3/4

     

    3/4   3/4

    1 1

    1 1/2 1 1/2

    2 2

     

     

     

     

     

     

    1

     

     

    1 1

    1 1/2

    2 2

    2 2

     

     

     

     

     

    1 1/2

     

     

     

    1 1/2   1 1/2

    2 2

    2 2

    3 3

     

     

     

     

    2

     

     

     

     

    2 2

    3 2

    3 3

    4 4

     

     

     

    3

     

     

     

     

     

    3 3

    4 3

    4 4

    6 6

     

     

    4

     

     

     

     

     

     

    4 4

    6 4

    6 6

    8 8

     

    6

     

     

     

     

     

     

     

    6 6

    8 6

    8 8

    10 10

    8

     

     

     

     

     

     

     

     

    8 8

    10 8

    10 10

    10

     

     

     

     

     

     

     

     

     

    10 10

    12 10

    12

     

     

     

     

     

     

     

     

     

     

    12 12

     

     

    7 Plant installation

    Good plant installation must begin as soon as the control valve is received on site, so that the valve is handled properly. Operators should adjust the control valve at every stage of installation; careless handling of control valves can greatly delay plant start-up.
    The following specific requirements should be considered:
    (1) The air supply used to operate a pneumatic control valve should be oil-free and dry, especially for valves with positioners.
    (2) A suitable filter should be fitted in the inlet piping of small-bore control valves to filter out impurities carried by the piping system and avoid damaging the valve.
    (3) When the valve is installed in the system, the body must be protected from excessive stress; this is particularly important for split-body valves.
    (4) Before initial start-up and after a shutdown for overhaul, a strainer should be fitted before the control valve to filter out scale, rust and other debris from the pipeline. Wherever possible, a spool piece should be provided in the piping system and the piping flushed before the control valve is installed.
    (5) For control valves operating in dusty environments, fit a rubber or plastic cover around the stem to protect its polished surface from damage.
    (6) All the manufacturer's instructions on adjustment and on the switch positions of auxiliary equipment must be followed. For example, do not forget the bypass switch in the bypass position of the valve positioner
    (7) It must be assumed that even a good design will inevitably trap high-pressure fluid when isolated, so it is recommended that where the potential energy of the trapped liquid is very hazardous, vent and/or drain valves be installed on each side of the control valve.
    (8) For valves in which a large quantity of high-pressure material accumulates, it is necessary to consider installing two vent and drain valves. Only a small quantity of material accumulates between the two valves, and the system pressure can be released gradually, so that pressure between the two drain or vent valves is repeatedly built up and released. Note that during this process the control valve must be open.
    (9) If the fluid being relieved is a hazardous gas, the vent line must be routed to a safe location.
    (10) If the control valve is to be removed from the system after installation, close the isolating valves and mark them. If the control valve contains hazardous fluid or contaminants, mark it accordingly so that proper cleaning can be carried out before the valve is removed.
    (11) Be sure to install the control valve in accordance with the flow direction arrow. If the direction indicated by the arrow supplied by the manufacturer is wrong, report it.
    (12) Read the specific instructions of each valve manufacturer before installation

    8 Notes on the use of tools and equipment

    1) How to assemble threaded pipe joints
    Threaded pipe joints (male and female threaded ends tightened together) are one of the most common methods of connecting pipe. First clean dirt from the internal and external threads of the fitting; a wire brush is recommended. Next, lubricate the threads with a little good thread lubricant, but apply the lubricant only to the male thread, so that surplus lubricant is not squeezed into the pipe and does not damage the seat or other parts. Take care with the wrench: do not use an oversized wrench, which tempts one to "lean on the joint". Screwing in too far causes damage, especially in the case of valve connections - do not try to screw the whole male thread into the fitting.


    2) How to assemble flange faces
    A flange face is assembled by bolting two flanges together with a gasket between their machined sealing faces. The correct steps for assembling a flange face are as follows:
    Clean all components. As with threaded connections, all parts must be wiped clean to ensure an effective installation. Wipe off the rust-preventive grease applied by the manufacturer to the flange with a solvent-soaked rag. Then wipe off all dirt and grit particles, and finally wipe the gasket clean.
    Align and support the pipe. When the pipe is in place, ensure that it is properly supported. For example, a valve must not be installed in an unsupported pipe section, as it cannot withstand large stresses. The flanges must be checked precisely with a spirit level, aligned horizontally with the pipe, with the flange faces vertical, so that the bolts can be tightened easily.
    Insert the gasket. To hold the flanges in the correct position, fit half the bolts at the bottom and put the gasket in place. Before inserting, coat the gasket with a little graphite grease or other recommended lubricant, so that the gasket is easier to remove even if the joint is opened later. Finally fit the remaining bolts so as to eliminate any concentrated stress. Tighten alternately and repeatedly until fully tightened. The flange face types must be the same; different flange faces assembled together cannot give a tight joint. Steel valves and fittings are usually made with raised-face flanges, whereas general piping materials of iron and bronze have flat-face flanges.