A self-operated control valve requires no external power source; it operates solely on the energy of the controlled fluid and keeps the controlled variable constant.
1. By function, self-operated pressure control valves are divided into upstream pressure control, downstream pressure control and differential pressure control.
Upstream pressure control regulates the pressure ahead of the valve and is also called a relief valve, with the pressure tapping point upstream; downstream pressure control has its tapping point downstream and is also called a pressure reducing valve. A differential-pressure self-operated valve is used to keep constant the pressure difference across the inlet and outlet of a piece of equipment or a circuit connected in series with it. When the differential pressure of the controlled object is greater than the set value, the valve closes down; when it is smaller than the set value, the valve opens up. The pressure drop across the valve itself varies with the available head of the external network, so as to keep the differential pressure of the controlled object constant.
2. By structure, self-operated control valves are further divided into direct-acting and indirect-acting types.
1) Direct-acting control valve, also called a spring-loaded control valve; it contains elastic elements such as springs, bellows and bellows-type thermobulbs, and works on the principle of balancing the elastic force against the feedback signal
2) Indirect-acting control valve: an additional pilot (pilot valve) amplifies the feedback signal, which then drives the actuator to move the main valve disc and so change the valve opening