Pneumatic actuators
    Linear travel
    Single-acting pneumatic actuators
    Cylinder-type actuators
    Direct-acting spring-diaphragm actuator                     Reverse-acting spring-diaphragm actuator
     
    Spring-diaphragm actuators have a smaller dead band than cylinder actuators, respond more sensitively and give higher accuracy.
     

    Part-turn (rotary) travel


     
    Rack-and-pinion type
     
    Scotch-yoke actuator
    Suitable for small and medium torques; requires little space.
     
    Suitable for large torques; requires more space.

Electric actuators
    Travel: there are three kinds - multi-turn, part-turn and linear.
    Multi-turn electric actuator (rotation angle > 360 degrees); used to drive valves whose stems move by screwing, such as gate valves, globe valves, throttle valves and diaphragm valves.
    Part-turn electric actuator (rotation angle < 360 degrees); the output shaft of the actuator turns through less than one revolution, i.e. less than 360 degrees, usually 90 degrees, to control the opening and closing of the valve.
    According to the mounting interface, such electric actuators are further divided into the direct-coupled type and the base-crank type.
    a) Direct-coupled: the output shaft of the electric actuator is mounted directly on the valve stem.
    b) Base-crank: the output shaft is connected to the valve stem through a crank. This type of electric actuator is suitable for butterfly valves, ball valves, plug valves, etc.
    Linear electric actuator: used to drive linear-travel valves whose stems move in a straight line, such as single-seat and cage valves, as shown on the right of the figure above. A linear intelligent electric actuator can be realised by combining a multi-turn intelligent electric actuator with a linear thrust unit.
    Function:
    There are two main categories: on-off type (open-loop control) and modulating type (closed-loop control).
    1. On-off type (open-loop control) - an on-off electric actuator generally performs open or close control of the valve: the valve is either fully open or fully closed, and such valves do not require accurate control of the medium flow rate. In particular, note that on-off electric actuators are further divided by structural form into split and integrated constructions. This must be stated at the time of selection, otherwise mismatches such as conflicts with the control system often occur during site installation.
    -a) Split construction (usually called the conventional type): the control unit is separate from the electric actuator, and the actuator cannot control the valve on its own; an additional control unit is required, generally an external controller or control cabinet. The disadvantages of this construction are that it is inconvenient to install as a system, the level transmitter adds wiring and installation costs, faults occur easily and when a fault occurs it is difficult to diagnose and repair, so the cost-performance is not ideal.
    -b) Integrated construction (usually called the integral type): the control unit and the electric actuator are packaged as one unit; no external control unit is needed for local operation, and for remote operation only the relevant control signals need to be output. The advantages of this construction are that it is convenient to install as a system, reduces wiring and installation costs and makes fault diagnosis and elimination easy. However, conventional integrated products also have many imperfections, which is why intelligent electric actuators have appeared; intelligent electric actuators are described later.
    2. Modulating type (closed-loop control) - a modulating electric actuator not only has the integrated construction of the on-off type and the function of accurately modulating the medium flow rate, but can also control the valve precisely.
    -a) Control signal type (current, voltage): the control signal of a modulating electric actuator is generally a current signal (4-20 mA, 0-10 mA) or a voltage signal (0-5 V, 1-5 V); the type and parameters of the control signal must be specified at the time of selection.
    -b) Operating mode (signal-to-open, signal-to-close): the operating mode of a modulating electric actuator is usually signal-to-open (taking 4-20 mA control as an example, signal-to-open means that a 4 mA signal corresponds to the valve being closed and 20 mA to the valve being open); the other is signal-to-close (taking 4-20 mA control as an example, signal-to-close means that a 4 mA signal corresponds to the valve being open and 20 mA to the valve being closed). Generally the operating mode must be specified at the time of selection, since many products cannot be modified after leaving the factory; the intelligent electric actuators produced by Aomei Valve Control can be modified at any time by on-site setting.
    -c) Fail-safe on loss of signal: fail-safe protection means that when the control signal is lost owing to a wiring fault or similar, the electric actuator drives the valve to a set protective position; the common protective positions are fully open, fully closed and stay-put.
     
    Selection key points:
    Linear- or quarter-turn actuator: linear travel or part-turn travel
    Nominal current [VAC] / [VDC] voltage: 24 V DC / 220 V AC
    Max. thrust [kN] / max. torque [Nm] required
    Modulating or 3-point control
    Failsafe (Yes/No): hold the safe position on power failure (yes/no)
    1. Select the electric actuator according to the valve operating torque: the torque needed to open and close a valve normally is determined by factors such as the valve size and working pressure, but because valve manufacturers differ in machining accuracy and assembly technique, valves of the same specification from different manufacturers need different torques, and even valves of the same specification from the same manufacturer differ. If the torque chosen for the actuator is too small the valve cannot be opened and closed normally, so a reasonable torque range must be chosen for the electric actuator. The output torque of the electric actuator should be 1.2 to 1.5 times the maximum operating torque of the valve.
    2. Determine the electrical parameters according to the electric actuator: because electrical parameters differ between actuator manufacturers, they generally have to be fixed at the design and selection stage; the main ones are motor power, rated current and secondary control circuit voltage. Neglect here often results in the parameters of the control system and the electric actuator not matching, causing faults such as no-load tripping, blown fuses and tripping of thermal overload relay protection during operation.
    3. Operating thrust: the main unit of an electric valve actuator is built in one of two ways: one without a thrust plate, which outputs torque directly; the other with a thrust plate, in which the output torque is converted into output thrust by the stem nut in the thrust plate.
    4. Number of turns of the output shaft: the number of turns of the output shaft of an electric valve actuator depends on the nominal diameter of the valve, the stem pitch and the number of thread starts, and is calculated from M = H/ZS (M is the total number of turns the actuator must provide, H is the valve opening height, S is the pitch of the stem transmission thread and Z is the number of thread starts on the stem).
    5. Stem diameter: for multi-turn rising-stem valves, if the stems of the valves to be fitted are larger than the maximum stem diameter the actuator can accept, an electric valve cannot be assembled. The bore of the hollow output shaft of the actuator must therefore be larger than the outside diameter of the stem of a rising-stem valve. For part-turn valves, and for non-rising-stem valves among the multi-turn valves, the stem diameter does not have to pass through, but the stem diameter and keyway dimensions should still be fully considered at the selection stage so that the assembly works properly.
    6. Output speed: if a valve opens and closes too fast, water hammer easily occurs. A suitable opening and closing speed should therefore be chosen according to the different service conditions.
    7. Electric valve actuators have a special requirement: they must be able to limit torque or axial force. Valve electric actuators usually use a torque-limiting coupling. Once the specification of the actuator is fixed, its control torque is also fixed. If it runs within the predetermined time the motor will not be overloaded.
    However, the following situations may cause overload:
    First, the supply voltage is low so the required torque cannot be obtained and the motor stops turning;
    second, the torque limiting mechanism is wrongly set so that it exceeds the stall torque, continuously producing excessive torque and stopping the motor;
    third, intermittent use causes heat to accumulate beyond the permissible temperature rise of the motor;
    fourth, for some reason the circuit of the torque limiting mechanism fails and the torque becomes excessive; fifth, the ambient temperature of use is too high, which relatively reduces the thermal capacity of the motor.
    In the past, motors were protected by fuses, overcurrent relays, thermal relays and thermostats, etc., but each of these methods has its advantages and disadvantages. For variable-load equipment such as electric actuators there is no absolutely reliable protection. A combination of methods must therefore be adopted; they fall into two groups:
    first, judging the increase or decrease of the motor input current;
    second, judging the heating of the motor itself.
    In either case the time margin allowed by the thermal capacity of the motor must be considered. The usual basic methods of overload protection are:
    1. Thermostats for overload protection of continuous running or inching operation of the motor;
    2. Thermal relays for protection against motor stalling;
    3. Fuses or overcurrent relays for short-circuit faults.

Electro-hydraulic actuators
    Composition: power section (hydraulic power unit), cylinder section, high-pressure oil lines
    1. Hydraulic power unit:
    Electrical control box: the control centre of the whole machine, responsible for receiving, monitoring and feeding back control signals and controlling the normal operation of the actuator.
    Valve block: responsible for the direction, pressure control and monitoring, and speed control of the hydraulic circuit. It is fitted with an adjustable relief valve to protect the hydraulic system. The red handle is the manual pressure relief valve.
    Manual section: provides manual control of the valve movement.
    Oil tank: stores the hydraulic oil; contains a filter and the high-pressure oil pump.
    Motor: the power source for the electro-hydraulic conversion, driving the high-pressure oil pump.
    Accumulator: stores hydraulic energy; when movement is required, its stored energy is released quickly to achieve fast action.
    2. Cylinder
    Converts hydraulic energy into mechanical energy to drive the valve. In split installation the cylinder is mounted on the valve, the hydraulic power unit is placed nearby, and the two are connected by oil lines.
    3. High-pressure oil lines
    Provide the power connection between the cylinder and the hydraulic power unit, forming a complete hydraulic circuit. Quick couplings at the ends of the lines allow rapid disconnection without oil leakage.

Gas-over-oil actuators
    Gas-over-oil (gas-hydraulic) valve actuators are commonly used on valves in long-distance natural gas pipelines; the pressure of the medium in the pipeline itself drives the valve to open or close. They have a simple working principle, safe and reliable control and strong environmental adaptability, and can meet the demanding all-weather outdoor conditions.

    The product uses natural gas from the pipeline directly as the motive gas source. The pneumatic-hydraulic system is designed for high pressure; after filtration and conditioning, the gas source enters the gas storage tank and the high-pressure pneumatic control valve block without pressure reduction. Under the action of the control signal, the high-pressure controlled gas enters the corresponding gas/liquid circuit, where the liquid medium, using the principle of equal-pressure transmission, produces synchronous gas-liquid transmission acting on the hydraulic cylinder of the valve actuator and so operates the valve.