Thermal power plants
    By total installed capacity:
    Small-capacity power plant (total installed capacity < 100 MW)
    Medium-capacity power plant (total installed capacity 100–250 MW)
    Medium-to-large capacity power plant (total installed capacity 250–600 MW)
    Large-capacity power plant (total installed capacity 600–1000 MW)
    Extra-large capacity power plant (total installed capacity > 1000 MW)

    By steam pressure and temperature:
    Medium- and low-pressure power plant (steam pressure 3.92 MPa, temperature 450 °C, unit output < 25 MW)
    High-pressure power plant (steam pressure 9.9 MPa, temperature 540 °C, unit output < 100 MW)
    Super-high-pressure power plant (steam pressure 13.83 MPa, temperature 540 °C, unit output < 20 MW)
    Subcritical-pressure power plant (steam pressure 16.77 MPa, temperature 540 °C, unit output 300–1000 MW)
    Supercritical-pressure power plant (steam pressure > 22.11 MPa, temperature 550 °C, unit output > 600 MW)
    Ultra-supercritical-pressure power plant (steam pressure > 33.5 MPa, 610 °C/630 °C, unit output > 600 MW)


    Thermal power plant flow diagram

    Combustion system

    Steam-water system


Nuclear power plants


    Nuclear power plant valves are an indispensable and important part of the safe operation of a nuclear power plant. Nuclear power valves include those used in the nuclear island (NI), the conventional island (CI) and the balance of plant (BOP) system.
    Because nuclear power plants have highly specific requirements for safety and reliability, the design and manufacture of nuclear power valves involve more testing requirements and stricter standards than conventional valves.
    By safety class, they are divided into nuclear safety class I, class II, class III and non-nuclear class; class I has the highest requirements and requires nuclear-grade certification.
    A nuclear power plant with two 1,000 MW units has about 30,000 valves of various types. The cost of nuclear power valves accounts for about 2% of the total investment in nuclear power construction.
    System: AP1000 nuclear island (NI): 7,500 valves, 35.5%
    Conventional island (CI): 11,200 valves, 50.9%
    BOP: 3,300 valves, 13.6%
    System: CPR1000 nuclear island (NI): 12,700 valves, 43.5%
    Conventional island (CI): 12,800 valves, 44.5%
    BOP: 3,400 valves, 11.7%
    System: Hualong One nuclear island (NI): 12,000 valves, 42.8%
    Conventional island (CI): 13,000 valves, 46.4%
    BOP: 3,000 valves, 10.7%

Power plant valves
    ● Condensate system

    1. Condenser recirculation control valve
    Like most centrifugal pumps, condensate pumps need a minimum flow to avoid overheating and to protect the pump from cavitation damage. A recirculation loop is therefore added from the pump outlet back to the condenser; the fluid in this loop is at 38–66 °C and 400–600 psi.
    The condenser recirculation valve must be able to absorb the entire pressure drop. Such a high pressure drop would cause cavitation in an ordinary valve.
    2. Deaerator level control valve
    The function of this valve is to maintain the deaerator level; it controls the flow of water from the condenser to the deaerator. The operating condition of this valve varies directly with load. At the very beginning of startup the pump load is small, the valve inlet pressure is high and the outlet pressure is low, because the pressure in the deaerator has not yet built up; in this case cavitation must be avoided and the flow is small. As the plant load increases, a large flow is required, and the condensate pump no longer maintains the same pump head at the larger flow. This causes the valve inlet pressure to drop.
    Meanwhile, the pressure in the line to the deaerator is building up, and this acts back on the valve. Maintaining a large flow under a relatively low pressure drop requires a valve with high flow capacity to reduce the resistance acting on the trim. Control requirements: provide the flow needed to keep the deaerator at normal water level, and raise the water temperature by adding steam so as to remove the gases dissolved in the water. Operating conditions: at the startup stage the flow is small and the differential pressure large; under normal conditions the flow is large and the differential pressure small — conditions similar to those of a feedwater valve. Valve requirements: effective cavitation resistance at low flow.

    ● Boiler feedwater system

    Operating requirements: during boiler startup the valve differential pressure can reach 100–300 kg (10–30 bar), with a small flow; in normal operation the differential pressure is smaller and the flow large, and the flow turndown ratio is 75:1–100:1. Note that hydrazine is generally added to the feedwater to remove dissolved oxygen; it reacts adversely with Stellite 6 alloy and similar alloys, so the valve trim should preferably not be treated by 316 stainless steel with Stellite hardfacing; 416 stainless steel may be used directly. 1. Boiler feedwater pump recirculation control valve (also called minimum flow control valve)
    During startup and shutdown, the feedwater pump must maintain a minimum flow to avoid damage. In addition, when the boiler feedwater flow exceeds the required amount, the excess is returned directly to the feedwater tank through the open recirculation valve. This ensures safe startup and operation of the boiler feedwater pump and eliminates pump damage caused by excessively low flow, excessive temperature rise and severe cavitation of the water. The pressure drop reaches 160–350 kg (16–35 bar); this valve withstands the largest differential pressure in the power plant system, and its flow is generally 30% of the normal flow.
    There is usually a very high pressure difference between the pump outlet and the feedwater tank, and this difference is reduced by a multi-stage pressure-reducing minimum flow valve. Accordingly, this valve must be able to operate both in on/off mode and in continuous control mode.
    The trim is of the balanced plug type with an anti-clogging design; pressure reduction is achieved through a labyrinth, cascade pressure reduction or a recirculating convection-type cage to avoid cavitation, and the number of pressure-reduction stages is selected according to the differential pressure. The sealing class must be Class V. The valve operates continuously while the pump is starting and stopping and closes once the pump has started normally, so it is usually fail-open.
    2. Main feedwater control valve
    If the feedwater pump has no speed control, the feedwater control valve serves as the control valve at 100% load. The feedwater control valve is often used during boiler load startup (with or without a variable-speed pump).
    - Stable control with good tracking performance
    - Sleeve and plug specially designed for feedwater valves, for tight shutoff and high durability
    - At small-opening control, standard labyrinth trim and multi-hole cage trim suppress cavitation
    In this valve there are two conflicting functions:
    - At full load, passing the maximum flow through the valve with the minimum pressure drop to achieve the expected optimum efficiency
    - During boiler startup, high differential pressure with small flow. To satisfy both functions above, the control valve needs a very large rangeability; this valve is equivalent to two valves in one. The 30% startup valve (bypass) usually uses labyrinth trim, while the multi-hole cage type is selected for full load, with Class V sealing.
    3. Boiler feedwater startup valve
    Many power plants use a startup valve together with a main valve to perform the above functions: the startup valve must handle small flow and resist cavitation, while the main valve must handle large flow with a small differential pressure. Labyrinth trim allows a single valve to cover the whole range.
    The requirements for this valve are:
    - Large rangeability and cavitation resistance at small flow
    - Low flow resistance at maximum flow
    - Leakage class meeting Class V shutoff
    - Fail-closed
    The operating conditions of the boiler feedwater startup valve are broadly similar to those of the boiler feedwater pump recirculation valve, namely a very high inlet pressure and full pressure drop. This valve requires cavitation protection and tight shutoff. Unlike the recirculation valve, it does not need to provide cavitation protection during the whole time the valve is in operation, so a cage valve with a labyrinth plug can meet these conditions. We generally recommend a small-bore angle valve with labyrinth trim.
    4. Desuperheating spray water control valve
    To control the temperature well at the final stage of the superheater, a high-efficiency spray water valve is needed. In steam desuperheating equipment it must also be taken into account that the cooling water sometimes has to be shut off; at that time a very high pressure acts on the components, with a large pressure drop across these valves. In view of such high pressure drops, various throttling plugs can be adopted to cope with them.
    At pressures above 300 psig, a multi-hole single-stage valve assembly is used; above 600 psig, a two-stage pressure-reducing assembly; above 900 psig, a multi-hole three-stage pressure-reducing assembly, in labyrinth trim form. The multi-stage and labyrinth trim commonly used in these spray water valves employ a quickly replaceable seat, which ensures convenient maintenance under heavy duty; with this design the seat and plug can be replaced in a very short time.
    5. Boiler periodic blowdown valve and continuous blowdown valve
    High temperature, high differential pressure, cavitation resistance; an angle valve is preferred.

    ● Main steam system

    The main steam system comprises the steam cycle components from the boiler outlet to the condenser: the steam passes from the superheater to the high-pressure turbine, then through the reheater to the low-pressure turbine, until its energy is fully spent, and returns to the condenser to begin a new cycle.
    Five important typical valve applications are found in this main steam system: the spray water control valves for superheater and reheater desuperheating, the high-pressure and low-pressure turbine bypass valves, and the sootblowing control valve.
    All of these involve complex operating conditions, including high pressure, high temperature, cavitation, noise, the type of boiler, the type of drum and whether the flow is straight-through; these have a great influence on the control valve.
    A once-through supercritical boiler is usually a relatively large unit and therefore needs relatively large valves, and it also operates at a higher main steam pressure. Besides the valves mentioned, some special valves are used on once-through boilers.

    1. High-pressure turbine bypass valve
    The high-pressure turbine bypass valve is of the high-pressure angle valve type, with the pressure reduced through the trim. The high-pressure turbine bypass system provides an alternative flow path for high-temperature, high-pressure steam, bypassing the turbine and flowing into the reheating section.

    When the turbine is not operating normally or during startup, this bypass system ensures stable operation of the whole boiler; steam then flows through the high-pressure bypass valve, and the spray water control valve keeps the bypass valve outlet temperature slightly above the normal high-pressure turbine outlet temperature.
    This control system must be able to open the valve quickly and to provide continuous feedback control according to the set temperature and pressure; the opening time is generally not more than 5 s. While the bypass valve is in service it must provide the same pressure drop and cooling function to protect the downstream reheater section of the boiler from damage, and must also be able to unload the turbine quickly without interrupting the boiler.
    A bypass is generally a device that discharges the main steam, without passing through the turbine, into the condenser after desuperheating and pressure reduction.
    The high- and low-pressure bypass systems have three functions: startup, overflow and safety.
    The structure is similar to an integrated desuperheater/pressure reducer, but with higher pressure and higher temperature and with higher requirements on materials and valve reliability. The valve is normally closed, requires a sealing class of Class V or better, and must open quickly within 3–5 s.
    Control requirements: adjust high-temperature, high-pressure steam to steam at a certain temperature and pressure; provide a bypass path for the turbine so that the boiler can operate independently of it. Operating conditions: desuperheating and pressure reduction of high-temperature, high-pressure steam. Valve requirements: thermal shock resistance, noise reduction and rapid response.
    2. Low-pressure turbine bypass valve
    The low-pressure bypass system provides a bypass path for the low-pressure turbine and controls the regulation of steam pressure and temperature, whether or not the high-pressure bypass system is in operation. The low-pressure bypass valve receives steam from the boiler reheater and regulates it so that it can be accepted by the condenser. The high temperature and pressure are reduced by throttling through the valve and by a large flow of desuperheating spray water. The temperature control requirement is not very stringent, since the purpose is only to protect the condenser. This protection is achieved by spray water and fast shutoff.
    Applications of the low-pressure bypass or the condenser usually have to take account of the process conditions of the low-pressure bypass: high pressure, high temperature, noise, tightness of valve closure and desuperheating requirements.

    3. Sootblowing control valve
    Good control valves are needed for sootblowing pressure control. During a sootblowing cycle the flow varies greatly, so the valve must have a large flow rangeability. When the sootblowing system is switched on and off, this control valve must respond quickly to avoid pressure surges and keep the piping safe. Because the temperature and pressure are very high, this application requires a very high valve pressure class; moreover, useful steam must not be wasted, so tight shutoff is required, making the requirements rather demanding. This sootblowing valve usually operates many times a day, especially when an isolation valve separates it from the steam line. Its service temperature must cover the entire operating temperature range. Apart from temperature effects, the high pressure drop causes strong noise and can damage and vibrate the plug; the plug designed for this application must therefore have very high performance. Taking all this into account, high noise and frequent operation are the important factors that cause problems, so we use a labyrinth plug to meet these conditions: it reduces the flow velocity and also provides a very wide rangeability. The trim uses an unbalanced design and a high-torque actuator to ensure tight shutoff.
    4. Auxiliary steam control valve
    Auxiliary steam for various equipment is obtained by reducing the pressure of main steam. Because the differential pressure is high, vibration and noise are produced; control valves of this type must avoid vibration and noise, and must also provide a wide flow control range, with a structure and materials able to withstand high-temperature, high-pressure steam.
    5. Deaerator limiting steam control valve
    The deaerator is similar to a heater (in which steam and feedwater are mixed), but is additionally designed to remove the non-condensable gases in the feedwater. These gases include oxygen and carbon dioxide, which damage and corrode the piping and the boiler tubes. The hot steam is usually mixed with the deaerator feedwater to bring the temperature to saturation, so that the non-condensable gases can be removed. For a drum boiler, the steam is taken from an auxiliary line off the main steam pipe; for a once-through boiler, the steam is taken from a flash tank or from the outlet of the high-pressure heater, at a somewhat lower pressure than in a drum boiler. The steam pressure is usually higher than required and must therefore be reduced; noise must be taken into account for this valve. The requirements for the deaerator limiting steam valve are rather demanding because the noise level is high, and special silencing equipment is used.
    6. Turbine gland seal steam pressure control valve
    7. Drain valves
    These are of ball valve and globe valve types; the body is generally forged, in materials such as A105, F22 and F91; sizes are generally 1–3 in, pressure classes 150–4500 lb, and the actuators are manual or electric.

    ● Heater drain system

    A typical power plant has two sets of feedwater heaters. The low-pressure heaters heat the water coming from the condensate pump until it is close to saturation before it enters the deaerator; the other set, the high-pressure heaters, heats the deaerated water coming from the feedwater pump, so that high-pressure, near-saturated deaerated water enters the boiler. The two systems work on the same principle; what differs is the heating medium: low-pressure heaters commonly use steam extracted from the low-pressure turbine, while high-pressure heaters use superheated steam from the reheating section. A feedwater heater is a shell-and-tube heat exchanger: the steam enters, cools and condenses into liquid, transferring its heat to the water in the process. The condensate level in the heater must be controlled efficiently, so the drain system is quite elaborate. In both heater systems, draining can cause a vacuum in the condenser: once the condensate is discharged to the condenser it loses pressure and flashes. The flashing fluid can damage the control valve and piping, so when selecting this valve the emphasis is on low flow resistance and on reducing the flow velocity as far as possible to minimize the damage caused by flashing. Material selection is equally demanding.
    1. High-pressure heater drain control valve
    For the high-pressure heater drain system, the control valve must ensure a stable pressure. Alloy steels A217-WC9 (A182-F22) or A217-C5 (A182-F5) are recommended first, with a carbide-treated plug; the material must resist erosion and impact. When the pressure class is as high as ANSI 1500 lb, an angle body is recommended to avoid erosion. A labyrinth plug keeps the flow velocity as low as possible.
    Control requirements: control the condensate level in the heater and discharge the condensate promptly, i.e. discharge at high level and drain at normal level. Operating conditions: the medium is saturated water; the differential pressure across the control valves between heaters is generally 6–30 kg (0.6–3 bar); the final-stage drain valve is connected directly to the condenser or deaerator. Valve requirements: resistance to flashing erosion, Class V or VI sealing, and the valve is usually fail-open.
    2. Low-pressure heater drain control valve
    For the low-pressure heater drain system, if a straight-through valve is selected, a WC9-bodied valve with a heat-treated plug is a good choice.
    3. Fuel oil and gas control valves
    Fuel oil: no seal leakage is permitted, and fast response is required in an emergency.
    4. High-pressure heater three-way valve
    This type of valve is designed to provide a bypass for high-pressure feedwater when a fault occurs in the high-pressure heater's piping, welds or drain system, or when the high-pressure heater needs maintenance.