Gas transmission and distribution process
    The task of a vaporization station is to receive liquefied natural gas, vaporize it, and supply it to users or use it for seasonal peak shaving. The vaporization station may be located within a storage and distribution station, in which case it is called a vaporization room.
    A CNG refueling station mainly receives gas from the trunk pipeline; after filtration, pressure regulation and metering, the gas enters the compressor for pressurization and, after drying, is stored in gas cylinders. When vehicles need refueling, the cylinder bank and the dispenser are controlled by a sequential program control panel to refuel the vehicle. A CNG refueling station may also be located within a storage and distribution station.
    After long-distance transmission, the gas passes through dust removal, pressure regulation, metering and odorization in the distribution station, then through the distribution networks of various levels and the gas pressure regulating devices, and is supplied to users safely and with guaranteed quality and quantity as required by the users.
    Gas pipelines can be divided by use into four categories: gas transmission mains, transmission and distribution mains, distribution branch pipes and user service pipes. (1) Gas transmission mains: pipelines that carry gas from the city gate station (or gas source plant) to the various high- and medium-pressure regulating stations in the city. They are generally high-pressure and sub-high-pressure pipelines. (2) Transmission and distribution mains: the collective term for transmission pipes and distribution pipes. Because among urban medium-pressure gas pipelines very few serve purely as transmission pipes and in most cases the transmission pipe also acts as a distribution pipe, they are collectively called transmission and distribution mains. ① Medium-pressure transmission and distribution mains: pipelines that carry gas from the gas source plant or storage and distribution station to the various gas-using areas of the city, including plant outlet pipes, station outlet pipes and main city road pipes; ② Low-pressure transmission and distribution mains: pipelines that carry gas from the regulating station to the gas supply area and distribute it to various users along the way.
    Low-pressure gas mains are generally not fitted with valves. When maintenance or fault handling is carried out on low-pressure pipelines, rubber plugs may be used to block the pipe, or a water seal may be used instead of a valve for shut-off. High-pressure and medium-pressure gas mains should be provided with sectional valves, and valves should also be installed at the starting points of their branch pipes. Valves should be installed on the inlet and outlet pipes of the regulating room, at both ends of gas pipelines crossing rivers, and on both sides where a pipeline crosses a railway or highway trunk line. Valves should be installed only where strictly necessary, so that when maintenance, fault handling or modification is carried out, individual pipe sections can be shut off and a large area of users is spared a gas supply interruption. Of course, every additional valve increases both the investment and the possibility of gas leakage. However, with valves installed, a fault will cut off gas to only a small number of users rather than a large number, which improves the reliability of gas supply through the network.
    City gate stations and storage and distribution stations should have the main functions of filtration, pressure regulation, metering, gas quality testing, safety venting, safety shut-off and automatic changeover between the duty line and the standby line, and are required to be designed with multiple safety measures on the premise of ensuring accurate pressure regulation and flow metering, so as to guarantee long-term, safe and stable gas supply.
    I. Classification of regulating stations (i) By regulation level: 1. high- and medium-pressure regulating station; 2. high- and low-pressure regulating station; 3. medium- and low-pressure regulating station (ii) By purpose: 1. district regulating station; 2. dedicated regulating station; 3. box-type regulating unit (iii) By installation arrangement 1. Above-ground regulating station 2. Underground regulating station II. The installation of pressure regulating equipment shall meet the following requirements: (1) Where natural conditions and the surrounding environment permit, it should preferably be installed in the open air, but a fence, guard rail or vehicle barrier should be provided; (2) When installed in a separate above-ground regulating box (wall-mounted type), the gas inlet pressure for residential and commercial users shall not exceed 0.4 MPa, and the gas inlet pressure for industrial users (including boilers) shall not exceed 0.8 MPa (3) When installed in a separate above-ground regulating cabinet (floor-standing type), the gas inlet pressure for residential, commercial and industrial users (including boilers) should preferably not exceed 1.6 MPa; (4) Where the requirements are met, it may be installed in a separate above-ground building; (5) Where above-ground conditions are restricted and the inlet pressure of the regulating equipment is not more than 0.4 MPa, it may be installed in a separate underground building or a separate underground box, provided that certain requirements are met; (6) Regulating equipment for liquefied petroleum gas and for gases with a relative density greater than 0.75 must not be installed in basements, semi-basements or separate underground boxes.
    Burners of industrial enterprises and public utility users generally consume a large amount of gas and can use higher-pressure gas; it is therefore more reasonable for such users to be connected to medium-pressure or high-pressure gas pipelines. This not only lightens the load on the low-pressure gas network but also makes full use of the gas pressure itself to induce air. For this reason, relatively high pressures may be used at both the inlet and the outlet of a dedicated regulating station. A separate room adjacent to the combustion equipment is usually used as the dedicated regulating station, as shown in Fig. 3-8. When the inlet pressure is medium or low and only one regulator with a connection diameter of less than 50 mm is installed, the regulator may also be installed in a corner of the workshop where the gas is used. If it is installed inside the workshop, it should be isolated with a fence. The regulating equipment and safety devices must be checked frequently for correct operation, and the gas tightness of the piping must also be checked frequently. A flow meter should be installed in a dedicated regulating station. A single-seat regulator that closes tightly should be selected, and a safety shut-off valve should be used as the safety device. The gas passage must be shut off not only when the pressure is too high but also when it is too low. This is because too low a pressure may cause the burner to go out and fill the combustion chamber with gas, forming an explosive gas mixture, which may lead to an accident when a flame approaches or ignition is attempted again.
    The load of a regulating station is the gas supply capacity it can handle. The load of a regulating station is determined as follows: 1. When a regulating station has only one regulator, it must handle the entire gas supply, and the regulator flow must meet the following requirements: (1) The rated flow of the regulator should be determined as a multiple (the multiplier is incomplete in the original) of the maximum hourly transmission capacity of the network served by that regulator; (2) The regulator flow must be able to meet the requirements of the maximum and minimum inlet gas pressures; (3) The pressure differential across the regulator should be determined by the difference between the minimum design pressure of the gas pipeline upstream of the regulator and the upper design pressure limit of the gas pipeline downstream of the regulator.
    Process requirements for regulating stations (or regulating boxes and cabinets): (1) District regulating stations serving a low-pressure network that is not looped, and user regulating units for continuous production, should preferably be provided with a standby regulator; in other cases a standby regulator may be omitted. A bypass pipe should be provided between the gas inlet and outlet pipes of the regulator, although a wall-mounted user regulating box need not have one; (2) Valves must be installed on the outdoor inlet and outlet pipes of high-pressure and sub-high-pressure gas regulating stations; (3) A filter should be installed at the regulator inlet; (4) An overpressure protection device should be provided at the regulator inlet (or outlet), preferably of the manual-reset type; (5) Indicating pressure gauges should be installed upstream and downstream of both the regulator and the filter; (6) A recording pressure instrument should be installed downstream of the regulator; the outlet of the vent pipe should be at least 1.0 m above the eaves of the regulating station. [17] The arrangement of regulators inside a regulating station shall meet the following requirements: The installation height of the regulator should allow convenient maintenance and inspection; when two or more regulators are arranged in parallel, the clear distance between the outer edges of adjacent regulators should preferably be greater than 1 m; the clear distance between the regulator and the wall, and the width of the main indoor passage, should both be greater than 0.8 m; when the gas piping inside and outside the regulating station is connected by insulating joints, the regulator and its auxiliary equipment must be grounded, with a grounding resistance of less than 100 Ω.
    When a city uses a low-pressure gas source and the scale of gas supply is not particularly large, the gas supply system usually adopts low-pressure gas storage, and a low-pressure storage and distribution station must be built to match it. The role of the low-pressure storage and distribution station is to store surplus gas during off-peak periods and, during peak periods, to draw gas from the low-pressure storage tanks and pressurize it into the medium-pressure network by means of the station's compressors, ensuring normal gas supply.
    When gas is supplied directly from a medium-pressure network (or a low-pressure network at a higher pressure) to domestic users, the gas pressure should be reduced by a user regulator directly to the rated pressure at which the gas appliance operates normally. In this case the user regulator is often installed in a metal box hung on the wall, as shown in Fig. 3-9. When a box-type regulating unit is installed among densely packed buildings, the safety vent valve may be omitted and only the safety shut-off valve used.




Valves for gas service
    There are many types of valves; those commonly used on natural gas pipelines include gate valves, globe valves, ball valves and butterfly valves.
    1. Filter When the inlet pressure is greater than 0.2 MPa, the allowable pressure loss (upper limit) of the filter is 10 kPa; when the inlet pressure of the regulating station is 0.2 MPa or less, the allowable pressure loss (upper limit) of the filter is 5 kPa. If the allowable pressure loss is exceeded, the filter should be overhauled and cleaned or its filter element replaced.
    2. Safety vent valve The venting pressure of a regulating station should be slightly higher than the shut-off pressure; the venting pressure is generally taken as about 1.3 times the rated outlet pressure.
    3. Safety shut-off valve The working pressure of the safety shut-off valve should be slightly higher than the safety venting pressure; depending on the circumstances, it may be taken as 1.1–1.2 times the venting pressure. For example, for a regulating station with an outlet pressure P2n = 1500 Pa, the working pressure of the safety vent valve may be taken as Pf = 2000 Pa, and the working pressure of the safety shut-off valve as Pshut-off = 2300 Pa.

Process parameters of regulating stations
    The purpose of a regulating station is to establish a pressure-stable network system downstream of it, meeting the needs of users for safe gas supply and use; at the same time, the regulating station itself must operate safely and reliably. For this reason, both the construction and the operation of a regulating station must meet the requirements of normal operating condition indices. The following mainly introduces several indices of station inlet and outlet pressure.
    Maximum inlet pressure P1max This is the highest inlet pressure permitted for the regulating station within the specified pressure range. The maximum inlet pressure P1max must be indicated on the nameplate of the regulator product. Users should select a regulator suited to their own network pressure regime according to the nameplate and the operating instructions.
    Minimum inlet pressure P1min This is the lowest inlet pressure permitted within the specified pressure range. A regulating station can only meet the requirements of a certain number of users; otherwise the station outlet pressure cannot be kept within the acceptable pressure range, which will affect safe and normal gas supply. If the station inlet pressure is lower than the minimum inlet pressure P1min, the supply capacity of the station will fall below the rated flow, resulting in too low an outlet pressure and an unreliable gas supply.
    Rated outlet pressure P2n When the outlet pressure of a regulating station is adjusted to a specified value within the specified pressure class range, this pressure value is the rated outlet pressure of the station. It may also be called the outlet pressure setpoint.
    Regulation accuracy δP2 This is the ratio of the deviation of the station outlet pressure from the rated outlet pressure P2n to the rated outlet pressure P2n. The smaller the regulation accuracy, the more stable the station's operating condition; the larger it is, the less stable the operating condition. According to the code, the permissible regulation accuracy is ±15% for stations with a low-pressure outlet, ±10% for stations with a medium-pressure class B outlet, and ±5% for stations with a high-pressure or medium-pressure class A outlet. If the regulation accuracy exceeds these percentages, the operating condition is unstable and the station's operating parameters are non-conforming. For example, for a regulating station with a rated outlet pressure of 1.5 kPa, the permissible regulation accuracy is ±15%, so its maximum outlet pressure is P2max = 1500 Pa × 1.15 = 1725 Pa, and its minimum outlet pressure is P2min = 1500 Pa × 0.85 = 1275 Pa.
    Rated flow Qn When the station inlet pressure is the minimum permitted value P1min and the outlet pressure is the minimum value P2min permitted by the regulation accuracy δP2, the gas flow of the regulating station is the rated flow Qn. If the regulating station operates normally and the inlet pressure is also normal, its flow will be greater than or equal to the rated flow. If the flow in the outlet network supplied by the station does not exceed this rated flow, the station outlet pressure will meet the regulation accuracy requirement; conversely, if the consumption in the network connected to the station outlet exceeds this rated flow, the outlet pressure P2 will drop and very likely fall below the minimum outlet pressure P2min, so that the regulation accuracy requirement cannot be met. This factor should be fully taken into account when determining the gas supply area and the number of households served by a regulating station; overloading will inevitably result in too low a supply pressure.
    Shut-off pressure Pb When the station flow gradually decreases to zero, the stable pressure reached on the outlet side is the shut-off pressure. Zero flow is an unfavourable operating condition for the regulator; it often causes the station outlet pressure to exceed the maximum outlet pressure P2 permitted by the regulation accuracy. The code therefore specifies an allowable shut-off pressure for regulating stations. The allowable shut-off pressure is Pb = 1.25 P2n for stations with a low-pressure outlet; Pb = 1.20 P2n for stations with a medium-pressure class B outlet; and Pb = 1.15 P2n for stations with a medium-pressure class A or high-pressure outlet. The shut-off pressure is a very important technical index of a regulating station. If the outlet pressure cannot be shut off, the network is liable to overpressure, causing accidents such as damage to gas meters, fire, explosion and poisoning. It is therefore important to keep the shut-off pressure below the allowable shut-off pressure.
    Maximum outlet pressure P2max This is the highest outlet pressure permitted within the specified regulation accuracy range. Minimum outlet pressure P2min This is the lowest station outlet pressure permitted within the specified regulation accuracy range. The rated outlet pressure P2n is a standard for the outlet pressure P2 determined according to the needs of the network and users. P2max and P2min are both defined relative to P2n and constitute the permissible pressure fluctuation range about the outlet pressure P2n; otherwise the regulation condition is non-conforming and cannot meet the actual needs of the network and users, and gas combustion will be unsafe and unstable and will not meet combustion hygiene standards.