Liquefaction temperatures of common hydrocarbon gases
methane -163 °C natural gas -161.2 °C ethylene -104 °C ethane -83.3 °C acetylene -84 °C propylene -47.7 °C propane -45 °C
Process flow:
LNG is delivered by cryogenic road tanker to the LNG satellite station. A horizontal dedicated unloading vaporizer installed at the unloading bay pressurizes the road tanker's tank, and the pressure differential is used to transfer the LNG to the cryogenic LNG storage tank of the satellite station. Under operating conditions the tank vaporizer raises the pressure of the LNG in the storage tank to 0.6 MPa. The pressurized cryogenic LNG enters an ambient-air vaporizer, where it exchanges heat with the air and is converted into gaseous natural gas with a rise in temperature; the outlet temperature is 10 °C below ambient temperature and the pressure is 0.45–0.60
MPa. When the natural gas temperature at the outlet of the ambient-air vaporizer does not reach 5 °C or above, it is heated in a water-bath heater; finally, after pressure regulation (regulator outlet pressure 0.35
MPa), metering and odorization, it enters the city gas distribution network and is supplied to various users.
LNG is the abbreviation of liquefied natural gas, whose main component is methane. Natural gas produced in the gas field is first purified and then liquefied under pressure at cryogenic temperature (-162 °C) to form LNG.
LNG is colorless, odorless, non-toxic and non-corrosive; its volume is about 1/600 of the volume of the same quantity of gaseous natural gas; its boiling point at atmospheric pressure is -161.5 °C, its storage temperature at atmospheric pressure is -162.3 °C, and its density is about 430 kg/m3.
The design temperature of the storage tank reaches -196 °C (the boiling point of LNG under normal conditions is -162 °C), whereas the temperature of the natural gas leaving the station is required to be no lower than ambient temperature minus 10 °C.
In the design of LNG vaporization stations, the codes commonly adopted are: GB 50028—93 Code for Design of City Gas Engineering (2002 edition); GBJ
16—87 Code for Fire Protection Design of Buildings (2001 edition); GB
50183—2004 Code for Fire Protection Design of Petroleum and Natural Gas Engineering; and the American NFPA 59A Standard for the Production, Storage, and Handling of Liquefied Natural Gas.
In normal operation the working temperature of the LNG storage tank is -162.3 °C; before first commissioning, the tank must be pre-cooled with liquid nitrogen at -196 °C.
BOG buffer tank, BOG heater: BOG stands for boil-off gas, i.e. the evaporated gas.
Ambient-air vaporizer
Water-bath natural gas heater: when the ambient temperature is low and the temperature of the gaseous natural gas at the outlet of the ambient-air vaporizer is below 5 °C, a water-bath natural gas heater is connected in series downstream of the ambient-air vaporizer to heat the vaporized natural gas.
Emergency vent gas (EAG) heater: when LNG is vaporized into gaseous natural gas, its critical buoyancy temperature is -107 °C. When the gaseous natural gas is warmer than -107 °C it is lighter than air and rises from the leak point and drifts away. When the gaseous natural gas is colder than -107 °C it is heavier than air; the cold gaseous natural gas accumulates downward and forms a flammable explosive mixture with air. To prevent the cold gaseous natural gas vented through safety valves from accumulating downward and forming an explosive mixture, one ambient-air emergency vent gas heater is installed: the vented gas is first heated in this heater so that its density becomes lower than that of air, and is then released at height. For LNG vaporization stations in southern China that are not equipped with EAG heaters, in order to prevent the cold LNG gas-liquid mixture released when a safety valve lifts from causing cold burns to operators, the vent lines of individual safety valves and of the storage tank should be connected to a centralized vent header.
Pressure regulation, metering and odorization equipment: the size of the pressure regulating equipment is selected according to the scale of the LNG vaporization station. Usually two pressure-regulating trains are installed, and self-operated regulators with a pilot and overpressure shut-off are selected. Tetrahydrothiophene is used as the odorant.
Valves in the process system must meet the pressure and flow requirements of LNG transmission, and must also have low-temperature performance down to -196 °C. Commonly used LNG valves mainly include pressurizing control valves, pressure-reducing control valves, emergency shut-off valves, cryogenic globe valves, safety valves and check valves. The valve material is 0Cr18Ni9.
Piping with a medium temperature ≤ -20 °C uses stainless steel seamless steel pipes for fluid service (GB/T
14976—2002), of material 0Cr18Ni9. All fittings are seamless stamped fittings of material 0Cr18Ni9 (GB/T
12459—90). Flanges are long-neck butt-welding steel pipe flanges with a male-and-female (tongue-and-groove) face (HG
20592—97), of material 0Cr18Ni9. Flange gaskets are spiral-wound metal gaskets of material 0Cr18Ni9. Fasteners are dedicated stud bolts and nuts of material 0Cr18Ni9.
For process piping with a medium temperature > -20 °C, where the nominal diameter is ≤ 200
mm, seamless steel pipes for fluid service (GB/T 8163—1999) of material No. 20 steel are used; where the nominal diameter is > 200 mm, welded steel pipes (GB/T
3041—2001) of material Q235B are used. All fittings are seamless stamped fittings of No. 20 steel (GB/T 12459—90). Flanges are raised-face neck butt-welding steel pipe flanges (HG
20592—97), of material No. 20 steel. Flange gaskets are flexible graphite composite gaskets (HG 20629—97).
LNG piping usually uses austenitic stainless steel pipes of material 0Cr18Ni9; although this material has excellent low-temperature mechanical properties, its cold shrinkage rate is as high as 0.003 [the sentence is incomplete in the original].
In normal operation the operating pressure of the LNG storage tank must be kept within the permitted range. In South China the normal working pressure range of LNG storage tanks is 0.3–0.7 MPa. When the pressure in the tank falls below the set value, the tank can be pressurized using the self-pressurization vaporizer and the self-pressurization valve. The lower limit of pressurization is determined by the opening pressure of the self-pressurization valve, and the upper limit by its automatic closing pressure, which is usually about 15% higher than the set opening pressure. For example, when LNG is used as the main source of city gas and the opening pressure of the self-pressurization valve is set at 0.6 MPa, the closing pressure of the valve is about 0.69
MPa, so the tank is pressurized by 0.09 MPa.
The maximum working pressure of the tank is limited by the set pressure (upstream pressure) of the automatic pressure-reducing control valve installed in the cryogenic vapour line of the tank. When the maximum working pressure of the tank reaches the set opening value of the pressure-reducing valve, the valve opens automatically to relieve the pressure, protecting the tank. To ensure that the pressurization valve and the pressure-reducing valve do not interfere with each other in operation, the closing pressure of the pressurization valve and the opening pressure of the pressure-reducing valve must not overlap, and a pressure difference of more than 0.05 MPa must be maintained. Taking into account the manufacturing tolerances of the two valves, the appropriate pressure difference should be determined during equipment commissioning.
During storage, LNG slowly evaporates because of "ambient heat in-leakage" through the tank (daily static evaporation rate ≤ 0.3% by volume), which causes the tank pressure to rise gradually and ultimately endangers the tank. To ensure safe operation of the tank, the design adopts three levels of overpressure protection: the tank pressure-reducing control valve, pressure alarm with manual venting, and safety valve lifting.
The protection sequence is as follows: when the tank pressure rises to the set opening value of the pressure-reducing control valve, the valve opens automatically to release gaseous natural gas; if the pressure-reducing valve fails and the tank pressure continues to rise to the alarm value, an alarm is given and the pressure is relieved by manual venting; if the pressure-reducing valve has failed and manual venting has not been opened, the safety valve lifts to relieve the pressure, ensuring safe operation of the LNG tank. For an LNG tank with a maximum working pressure of 0.80 MPa, the design pressure is 0.84 MPa, the set opening pressure of the pressure-reducing control valve is 0.76 MPa, the tank alarm pressure is 0.78 MPa, the safety valve opening pressure is 0.80 MPa and the safety valve relieving pressure is 0.88 MPa.
To prevent rollover of LNG from causing accidents, stratification of the LNG in the tank must be prevented. The following measures are commonly adopted.
① Store LNG from different gas sources separately, to avoid stratification caused by density differences.
② To prevent density differences between the LNG filled into the tank at different times, the following filling methods are used:
a. when the LNG in the tanker and the LNG in the tank have similar densities, fill through the lower liquid inlet of the tank; b. when light LNG from the tanker is filled into a tank containing heavy LNG, fill through the lower liquid inlet of the tank;
c. when heavy LNG from the tanker is filled into a tank containing light LNG, fill through the upper liquid inlet of the tank.
③ Mixing nozzles and perforated pipes are used on the tank's inlet line, so that the newly filled LNG mixes thoroughly with the existing LNG and stratification is avoided.
④ For LNG stored over long periods, periodic tank switching (pumping over from one tank to another) is used to prevent stratification caused by standing.
Operation monitoring and safety protection
① Emergency shut-off at high and low liquid level of the LNG tank. A pneumatic emergency shut-off valve is installed on both the liquid inlet and the liquid outlet line of each LNG tank, so that in an emergency the inlet and outlet liquid lines can be shut off from the unloading bay, the tank area or the control room. Pipeline safety valves are installed respectively on the inlet and outlet lines of the inlet emergency shut-off valve and on the outlet line of the outlet emergency shut-off valve, to relieve the pressure in the pipeline after the emergency shut-off valve has closed.
② Over-temperature alarm downstream of the vaporizer, with interlocked shut-off of the vaporizer inlet liquid line. The emphasis is on detecting, alarming and interlocking on the gas temperature at the vaporizer outlet. In normal operation at rated load, the gas outlet temperature of the vaporizer is 10 °C below ambient temperature. When the vaporizer frosts excessively or fails, the vaporizer is controlled by over-temperature detection and alarm together with interlocked closing of the vaporizer inlet liquid line.
③ Natural gas leak concentration detectors are installed in the LNG process unit area. When the concentration exceeds the alarm limit, audible and visual alarm signals are given, and the inlet and outlet motor-operated valves can be closed quickly from the control room.
④ Regulators with overpressure shut-off are selected. When the regulator outlet pressure exceeds the limit, automatic changeover takes place. A safety relief valve is installed downstream of the regulator to vent safely on overpressure.
⑤ All natural gas outgoing lines are fitted with motor-operated valves that can be closed quickly from the control room.
⑥ The pressure downstream of the outgoing valve exceeds the set alarm pressure [the sentence is incomplete in the original].